Manual 26489V1
Vertex-Pro Motor-Driven Compressor Control
Woodward
65
8.3—Discrete I/O FTM
8.3.1—24/12 Discrete Module (Phoenix Contact)
This relay module is for use in ordinary or non-hazardous locations
only.
The 24/12 Discrete Module is used with 48/24 Discrete Combo Module (see
Chapter 6 MicroNet module information and Appendix A for FTM part number).
The 24/12 Discrete Module has 24 discrete inputs connections and 12 SPDT
relay outputs. Two relay modules connect to one 48/24 Discrete Combo Module.
Each FTM uses one MicroNet High Density Analog/Discrete cable to connect it
with the 48/24 Discrete Combo Module (see Appendix A for part numbers). This
relay module incorporates an I/O lockout relay that will de-energize all of the
relays if de-activated by the I/O lock signal from the DO module. All field
connections use removable connectors for ease in replacing module in the field.
All relays are field replaceable.
Relays (see Appendix A)
Output Rating:
10 A @ 28 Vdc Resistive
3 A @ 150 Vdc Resistive
10 A @ 115 Vac Resistive
10 A @ 240 Vac Resistive
3 A @ 28 Vdc Inductive
1.2 A @ 150 Vdc Inductive
6 A @ 115 Vac Inductive
3 A @ 240 Vac Inductive
Содержание Vertex-Pro
Страница 10: ...Vertex Pro Motor Driven Compressor Control Manual 26489V1 viii Woodward ...
Страница 72: ...Vertex Pro Motor Driven Compressor Control Manual 26489V1 62 Woodward Figure 8 2 24 8 Analog FTM Schematic ...
Страница 74: ...Vertex Pro Motor Driven Compressor Control Manual 26489V1 64 Woodward Figure 8 4 Analog Combo FTM Schematic ...
Страница 103: ...Manual 26489V1 Vertex Pro Motor Driven Compressor Control Woodward 93 Appendix C Declarations ...
Страница 104: ...Vertex Pro Motor Driven Compressor Control Manual 26489V1 94 Woodward ...
Страница 105: ...Manual 26489V1 Vertex Pro Motor Driven Compressor Control Woodward 95 ...
Страница 106: ...Vertex Pro Motor Driven Compressor Control Manual 26489V1 96 Woodward ...
Страница 107: ...Manual 26489V1 Vertex Pro Motor Driven Compressor Control Woodward 97 ...
Страница 111: ......