Vertex-Pro Motor-Driven Compressor Control
Manual 26489V1
68
Woodward
Chapter 9.
Installation and Replacement Procedures
9.1—Pre-Installation Information
9.1.1—Storage
Store MicroNet™ controls and associated parts between –20 and +70 °C
(–4 and +158 °F) at a maximum relative humidity of 90% non-condensing. If
modules (especially power supplies) are to be stored for a long time, apply
operating power to them at least once every 18 months. This is done to re-form
the aluminum electrolytic capacitors, and will prevent them from overheating
upon initial power up after extended storage.
9.1.2—Unpacking
Unpack each part of the system carefully. Check the units for signs of damage,
such as bent or dented panels, scratches, or loose or broken parts. If any
damage is found, notify the shipper immediately.
9.1.3—Unit Location
Consider the following when selecting a cabinet location for mounting the
MicroNet:
Make sure the MicroNet unit(s) are mounted in a dry location, protected
from water and condensation.
Make sure the ambient temperature of the system location is not lower than
0 °C (32 °F) or higher than 55 °C (131 °F) and that the relative humidity is
not over 90%, non-condensing. (
NOTE
—For NTCPU 0–50 °C)
Provide adequate ventilation for cooling the units. If the units must be
mounted near heat-producing devices, shield them from the heat.
Do not install the units or their connecting wires near high-voltage/high-
current devices or inductive devices. If this is not possible, shield both the
system connecting wires and the interfering devices or wires.
If the selected location does not already have a conductor to a good earth
ground, provide one.
This equipment is suitable for Class I, Division 2, Groups A, B, C, and D or
non-hazardous locations only. The 24/12 and 16 channel relay modules are
for use in ordinary or non-hazardous locations only.
Содержание Vertex-Pro
Страница 10: ...Vertex Pro Motor Driven Compressor Control Manual 26489V1 viii Woodward ...
Страница 72: ...Vertex Pro Motor Driven Compressor Control Manual 26489V1 62 Woodward Figure 8 2 24 8 Analog FTM Schematic ...
Страница 74: ...Vertex Pro Motor Driven Compressor Control Manual 26489V1 64 Woodward Figure 8 4 Analog Combo FTM Schematic ...
Страница 103: ...Manual 26489V1 Vertex Pro Motor Driven Compressor Control Woodward 93 Appendix C Declarations ...
Страница 104: ...Vertex Pro Motor Driven Compressor Control Manual 26489V1 94 Woodward ...
Страница 105: ...Manual 26489V1 Vertex Pro Motor Driven Compressor Control Woodward 95 ...
Страница 106: ...Vertex Pro Motor Driven Compressor Control Manual 26489V1 96 Woodward ...
Страница 107: ...Manual 26489V1 Vertex Pro Motor Driven Compressor Control Woodward 97 ...
Страница 111: ......