29
When using load sharing a maximum of three parallel compressor controls can
be connected by CAN communication. Redundant CAN communication can be
performed by using both CAN #1 and CAN #2 ports on the CPU module. Figure
5-11 is the example of single CAN communication with redundant CPU hardware
configuration.
Vertex-
Pro
Termination
Resistor
(Female)
1635-1465
M12 to 7/8" Drop Cable
5417-1120
7/8" Tee
1635-1463
Thick Trunk Cable
5417-1113 or Similar
M
F
F
M
F
F
CAN#1 Right
CAN#1 Left
EARTH Ground the overall cable
braid at the cabinet exit point
M12 to 7/8" Drop Cable
5417-1120
or Similar
Vertex-Pro
M
F
F
M
F
F
CAN_R CAN_L
Termination
Resistor (male)
1635-1464
Vertex-Pro
M
F
F
M
F
F
CAN_R CAN_L
Figure 5-11—CAN Communication Connection Example
5.1.10—CAN Cable Specification
Thick cable is preferred and recommended for all uses. Most CAN / DeviceNet™
(trademark of ODVA, Inc.) cable is not rated for temperatures above 80 °C so be
careful during installation to avoid hot routing areas. Always use shielded cables
for improved communications in industrial environments.
Impedance:
120
Ω
10% at 1 MHz
DC resistance:
< 7
per 1000 ft.
Cable capacitance:
12 pF/ft at 1 kHz
Propagation delay
1.36 ns/ft (maximum)
Data Pair:
19 strands, 1.0 mm² corresponds to 18 AWG, individually tinned, 3 twists/foot
Power Pair:
19 strands, 1.5 mm² corresponds to 15 AWG, individually tinned, 3 twists/foot
Drain / Shield Wire:
19 strands Tinned Copper shielding braid or shielding braid and foil
Cable type:
twisted pair cable. 2x2 lines
Bend Radius:
20x diameter during installation or 7x diameter fixed position
Signal attenuation:
0.13 dB/100 ft @ 125 kHz (maximum)
0.25 dB/100 ft @ 500 kHz (maximum)
0.40 dB/100 ft @ 1000 kHz (maximum)
Содержание Vertex-Pro
Страница 10: ...Vertex Pro Motor Driven Compressor Control Manual 26489V1 viii Woodward ...
Страница 72: ...Vertex Pro Motor Driven Compressor Control Manual 26489V1 62 Woodward Figure 8 2 24 8 Analog FTM Schematic ...
Страница 74: ...Vertex Pro Motor Driven Compressor Control Manual 26489V1 64 Woodward Figure 8 4 Analog Combo FTM Schematic ...
Страница 103: ...Manual 26489V1 Vertex Pro Motor Driven Compressor Control Woodward 93 Appendix C Declarations ...
Страница 104: ...Vertex Pro Motor Driven Compressor Control Manual 26489V1 94 Woodward ...
Страница 105: ...Manual 26489V1 Vertex Pro Motor Driven Compressor Control Woodward 95 ...
Страница 106: ...Vertex Pro Motor Driven Compressor Control Manual 26489V1 96 Woodward ...
Страница 107: ...Manual 26489V1 Vertex Pro Motor Driven Compressor Control Woodward 97 ...
Страница 111: ......