The application mode for Mobile Systems is fixed to GCB.
Parameter
The following LogicsManager can be used to selected the operation condition from the
Genset.
ID
Parameter
CL
Setting range
[Default]
Description
12894
Parallel mode
2
Determined by
LogicsManager
[(0 & 1) & 1]
Once the conditions of the
LogicsManager have been
fulfilled the generator is
selected for Mains parallel
operation.
Notes
The application mode
"GCB" is internally used
and the MCB is assigned as
closed independent from
the DI status.
The generator operates
mains parallel and the
mains voltage should be
connected for the mains
monitoring during parallel
operation.
12895
Isolated mode
2
Determined by
LogicsManager
[(0 & 1) & 1]
Once the conditions of the
LogicsManager have been
fulfilled the generator is
selected for isolated
operation.
Notes
The application mode
"GCB" is internally used
and the MCB is assigned as
open independent from the
DI status.
The generator operates
with frequency and voltage
controller in isolated
operation
12896
Mains
synchronization
2
Determined by
LogicsManager
[(0 & 1) & 1]
Once the conditions of the
LogicsManager have been
fulfilled the generator
synchronize to the utility
39
easYgen-3000XT Series
37595
2 Additional Functionality
2.1.2 Mobile Systems