There is a priority selection between the LogicsManager for the Parameter Sets and the
default "Parameter Set 1" is used, if more than one parameter set is enabled
simultaneously.
LogicsManager
87.63 LM:
Parameter
Set 2
False
True
False
False
True
False
True
87.64 LM:
Parameter
Set 3
False
False
True
False
True
True
True
87.65 LM:
Parameter
Set 4
False
False
False
True
False
True
True
Parameter
Set 1
Parameter
Set 2
Parameter
Set 3
Parameter
Set 4
Parameter
Set 1
Parameter
Set 1
Parameter
Set 1
2.1.2
Mobile Systems
Introduction
The Mobile Systems functionality is used for the maintenance from utility substations. The
load from the utility substation can be transfer to a mobile Genset during maintenance.
For this the Genset synchronize to the utility and operates mains parallel. The operator
increases the load from the Genset in order to reduce the utility load. After that the utility
breaker can be opened manually and the load is supply by the mobile Genset.
After the maintenance the Genset synchronize back to the utility with phase matching
synchronization. With synchronous condition the operator closes the utility breaker
manually and with the unloading from the generator the load will be back-transferred to
the utility.