ID
Parameter
CL
Setting range
[Default]
Description
configured to "Phase-
neutral")
3Ph 3W
Measurement is performed
Line-Line (Delta connected
system). Phase voltages
must be connected for
proper calculation.
Measurement, display, and
protection are adjusted
according to the rules for
Delta connected systems.
Monitoring refers to the
following voltages:
• VL12, VL23, and VL31
•
1Ph 2W
Measurement is performed
Line-Neutral (WYE
connected system) if
parameter 1858 is
configured to "Phase -
neutral" or Line-Line (Delta
connected system) if
parameter 1858 is
configured to "Phase -
phase".
Measurement, display, and
protection are adjusted
according to the rules for
phase-phase systems.
Monitoring refers to the
following voltages:
• VL1N and VL12
•
1Ph 3W
Measurement is performed
Line-Neutral (WYE
connected system) or Line-
Line (Delta connected
system). The protection
depends on the setting of
parameter 1770.
Measurement, display, and
protection are adjusted
according to the rules for
single-phase systems.
28
easYgen-3000XT Series
37595
2 Additional Functionality
2.1.1 Switchable Parameter Sets