FD-6045-CE and FD-8645-CE
Fire Deck Installation and Operation Manual
PG
26
OF
32
M0042.13 JULY 2019
OPERATIONAL SEQUENCE
Power ON�
Pilot lights�
ICS2 Module powers
Igniter and opens Pilot
valve�
Burner remains ON
until oven Controller is
turned OFF�
ICS2 Module senses
Pilot flame, Turns OFF
Igniter, Valve opens,
Burner lights, Dome
Flame light
comes ON�
Pilot does not light,
ICS2 Module times
out, Type 2
Controller flashes
“chec”�
Note:
Ovens equipped with 2 Radiant burners will
have an additional ignition module–ICS3, which will be
powered at the same time as the ICS2 module described
above� The operation sequence is identical to that of
ICS2� However, as long as either radiant burner lights, the
Dome Flame Indicator light will come on�
Note:
Ovens equipped with 2 Radiant burners will have a third ignition
module–ICS3, which will be powered at the same time as the ICS2 module
described above� The operation sequence is identical to that of ICS2� How-
ever, as long as either radiant burner lights, the Dome Flame Indicator light
will come ON and the Controller will power ICS1 as necessary�
Power ON�
ICS2 Module (Radiant burner)
powers Igniter and opens
Pilot valve�
ICS2 senses Pilot
flame, Igniter OFF,
ICS2 powers SV-2
Valve, Radiant
burner lights, Dome
Flame Indicator light
comes ON�
Pilot lights�
Pilot does not light, ICS2
Module times out�
Pilot lights, ICS1 senses
Pilot flame,
Igniter OFF� ICS1 pow-
ers SV-1 valve, Infrared
burner lights, Hearth
Heat light comes ON�
Radiant burner re-
mains ON until oven
is turned OFF�
Floor temperature
above Hearth Set
Point – No action�
Floor temperature
below Hearth Set Point
– Controller sends
power to ICS1– ICS1
powers Igniter and
opens Pilot valve�
Floor reaches Hearth Set Point – Controller turns
OFF power to ICS1 to turn OFF IR burner�
Pilot does not light,
ICS1 times out,
Controller flashes
“chec”�
RFG-(W) CE OVEN BURNER OPERATION SEQUENCE
RFG-IR-(W) CE OVEN BURNER OPERATION SEQUENCE
Power ON�
Pilot lights, ICS1 senses
Pilot flame, Ignitor OFF,
ICS1 powers SV-1 valve,
Infrared burner lights,
Hearth Heat light comes
ON�
Floor temperature below
Hearth Set Point –
Controller sends power
to ICS1 Module, ICS1
powers Igniter and
opens Pilot valve�
Floor reaches Hearth Set
Point, Controller turns
OFF power to ICS1 to
turn OFF IR burner�
Pilot does not light,
ICS1 Module times
out� Type 2
Controller flashes
“chec”�
Pilot does not light,
ICS1 Module times
out, Type 2
Controller flashes
“chec”�
Note:
Primary heat source for this model is the
wood fire�
W-IR CE OVEN BURNER OPERATION SEQUENCE