Planning
3066501_201910
WOLF GmbH | 29
DWTK
≥ 150 cm²
min. 2500
min. 600
max.1000
min. 605
max.2000
min. 600
max.1000
min. 600
max.1000
Table 4.12 Cascade control with header
Maximum height - flue gas routing with header
Conditions for calculation:
➠
Maximum length of flue between individual heat generators 1 m
➠
Maximum length of flue after the final heat generator 2 m
➠
Geodetic height: 325 m
► If the conditions at the installation site are different, an individual calculation is required.
Number
2 x
2 x
3 x
4 x
2 x
3 x
4 x
COB-2
29
29
29
29
40
40
40
Installation
Type B23
Flue internal diameter
DN
110
160
160
160
160
160
160
Total flue gas mass flow rate
g/s
26.6
26.6
40.0
53.3
35.0
52.5
70.0
Maximum flue gas
temperature
°C
76
83
Maximum effective building
height
m
30
Table 4.13
Maximum height - flue gas routing with header
Min.
Min.
Max.
Max.
Max.
Max.
Min.
Min.
Min.