Installation
40 | WOLF GmbH 3066501_201910
5.9.2
Installing the flue gas damper (cascade operation only)
Fig. 5.16 Flue gas damper
q
Appliance connection with flue gas test port
w
Flue gas damper
► Insert the flue gas damper
(2)
fully into the appliance collection with flue gas test port
(1)
.
► Connect the flue gas damper to the power supply (
5.10.6 Connect the flue gas damper to the power
supply (cascade operation only).
5.9.3
Installing the roof outlet
650
550-1050
1250
Ø 130
Fig. 5.17 Roof outlet [mm]
q
Flat roof collar
w
Adaptor for “Klöber base panels”
e
Universal tile
r
Mounting bracket
t
Roof outlet
i
The roof outlet
(5)
may only be installed in its original condition. Modifications are not permissible.
Universal tile
(3)
can be combined with adaptor for “Klöber base panels”
(2)
.
► Affix flat roof collar
(1)
into roof cover.
► When using universal tile
(3)
, observe the installation instructions on the cowl regarding roof pitch.
► Guide the roof outlet
(5)
through the roof from above.
► Secure vertically with mounting bracket
(4)
to a rafter or brickwork.
5.10 Electrical connection
DANGER
Risk of electrical voltage even when the ON/OFF switch is set to OFF!
Danger of death from electrocution
► Isolate the entire system from the power supply across all poles (e.g. by removing the mains fuse
or by means of a main switch or heating emergency stop switch).
► Check that the appliance is isolated from the power supply.
► Safeguard the system against reconnection.
5.10.1 Power supply
Power cable: flexible, 3 x 1.0 mm² or rigid, up to 3 x 1.5 mm²
The maximum current carrying capacity of the outputs is 1.5 A. Do not exceed a total of 4 A.
► In case of a permanent connection, connect the power supply via a mains isolator (e.g. fuse, heating
system emergency stop switch) that ensures at least 3 mm contact separation.