Fault
3066501_201910
WOLF GmbH | 67
Fault
code
Message
Cause
Remedy
24
Speed fault
Fan
– Set fan speed is not achieved.
► Press reset button.
► Switch power supply OFF/ON.
► Check power cable to fan.
► Check fan.
26
Fan fault
– The fan does not stop.
► Check power cable to fan.
► Check fan.
► Press reset button.
27
Faulty stratification
sensor
– Faulty stratification cylinder
sensor or lead.
► Check sensor.
► Check lead.
29
Differential pressure
sensor short circuit
– Differential pressure sensor
or cable defective.
► Test sensor.
► Check lead.
► Press reset button.
30
CRC
Burner control unit
– The EEPROM data set is invalid.
► Switch power supply OFF/ON.
If fault persists:
► change burner control units.
34
CRC BCC-ID incorrect
in CM-EEPROM
– Boiler coding card fault.
► Replace boiler coding card.
35
BCC not correct
– Boiler coding card has been
removed or incorrectly inserted.
► Refit the correct boiler coding
card.
36
CRC BCC-ID incorrect
in the BCC
– Boiler coding card fault.
► Replace boiler coding card.
37
Incorrect BCC
– The boiler coding card is
incompatible with the burner
control unit.
► Insert the correct boiler coding
card.
► Press reset button.
38
BCC update required
– Boiler coding card fault, PCB
requires a new boiler coding card
(if replacement part).
► Reinsert boiler coding card.
► Check boiler coding card.
39
BCC system error
– Boiler coding card fault
► Replace boiler coding card.
42
Condensate pump not
pumping
– Condensate pump is defective.
– Drain line is blocked.
– No power supply to the
condensate pump.
► Check the condensate pump.
► Check drain line.
► Check power connector and
fuses.
52
max. cylinder heating
time
– The cylinder heat time lasts longer
than permitted.
► Check DHW sensor (cylinder
sensor) and sensor lead.
► Vent cylinder.
► Extend cylinder heating time.
Press reset button.
78
Header sensor fault
– Faulty header sensor or lead.
► Check sensor.
► Check lead.
85
Relay test
– Relay test failed.
► Switch power supply OFF/ON.
► Press reset button.
90
BCU communication
– Emergency stop via ChipCom.
– Communication between control
unit PCB and burner control unit
disrupted.
► Press reset button.
► Check connection between
burner control unit and HCM-2
board.
91
Bus communication
– Duplicated eBus address.
► Assign the eBus address once.
95
Prog. mode
– Burner control unit is controlled
by PC.
No action.
96
Reset
– Reset button pressed too many
times.
► Switch power supply OFF/ON.
99
System error
Burner control unit
– Internal burner control unit fault.
► Switch power supply OFF/ON.