Installation
3066501_201910
WOLF GmbH | 39
Fit disconnect device
► Slide the disconnect device
(6)
(
Fig. 5.14 Example: balanced flue [mm]
) fully into the socket
(5)
.
► Slide the next balanced flue pipe
(5)
50 mm
into the socket of the disconnect device
(6)
.
► Ensure that the balanced flue pipe
(5)
is fully secured in this position, e. g. with a pipe clamp
(7)
or with
a locking screw on the air side.
Calculating clearance and offset
A
B
A
Fig. 5.15
Balanced flue pipe length
A
Clearance
B
Offset
q
Balanced flue pipe length
w
45° bend
e
Bend 87°
► Determine distance
(A)
.
► Balanced flue pipe
(1)
length always approximately 100 mm longer than clearance
(A)
.
► Take the offset
(B)
into account.
Bend
B
87°
At least 204 mm
45°
At least 93 mm
Table 5.1 Offset bend
Installing a balanced flue in an existing chimney/duct
► Make sure that there is appropriate clearance between the outside of the flue and the wall of the duct
Fig. 4.6 Minimum shaft size [mm]
).
► Flue lines, retaining straps and spacers must be installed in channels and ducts in such a way that the
ventilated cross-section can be inspected and cleaned.
► Close cleaning apertures in ducts with chimney cleaning covers which have been assigned an
approved test mark.
► The outlets of flue lines in ducts must be designed so that the following requirements are met:
– no ingress of precipitation
– secondary ventilation can flow freely
► It must be possible to remove removable covers without tools and they must be secured to prevent
them falling.