Electrical installation
INTORQ | BA 14.0196 | 04/2016
35
5
Electrical installation
5.1
Important notes
DANGER
There is a risk of injury by electrical shock!
❚
The electrical connections must only be made by skilled personnel!
❚
Only carry out connection work when no voltage is applied (no live parts)! There is a risk of
unintended start-ups or electric shock.
NOTICE
❚
Make sure that the supply voltage corresponds to the data on the nameplate.
❚
Voltages must be adjusted to the local environment!
NOTICE
❚
If an emergency stop is carried out without the required suppressor circuit, the control unit
may be destroyed.
❚
Observe the correct polarity of the suppressor circuit!
NOTICE
❚
To functionally test the individual brake circuits, the power supply must be able to be
switched off individually. For a new over-energizing during switch-on, it is also necessary
to open switches K1/K3.
❚
The protective circuitry contained in the INTORQ switching device BEG-561-
-
(terminals 3 and 4) is not permitted for use in the lift system. The protective circuitry
must be connected parallel to the brake coil (
NOTICE
❚
Only operate the brake with a holding current reduced to 25 % of P
max
!
❚
You can use the INTORQ switching device BEG-561-
-
for this purpose.