The “Max. unexpected over current” should be set to 0 after the
ML has been opened and closed 5 times and after you ensured
that the windows are properly closed.
Closing the motor line 5 times gets the motors to establish their
Zero (closed) position. Setting the parameter to 0 ensures that
the motors will never change their Zero position and always
report an error if they receive the command but cannot reach
their closed position.
Confirm with check mark.
Configure the rest of the motor lines in the same way.
Once all the motor lines have been configured the warning icons
will disappear.