34/47
Set “Line B (smoke detector) smoke opening pos.”
In most cases windows must open 100% in Alarm but there are
cases where window must be closed (0%) when the smoke
detectors trigger the alarm.
Reduce the “Line B (smoke detector) smoke opening pos.” from
100% to 0%
by pressing either “-10” or “Min.”.
Confirm with check mark.
Set the
“Use comfort commands” to “No”.