Figure 7
overview of the smoke zone, motor groups and motor lines.
Figure 8
overview of the smoke panel and how the different components are connected it.
3.3 Configuration
See Example 2 for the configuration of the MotorLines, the Motor Groups, the keypads, the alarm signal from
the BMS and the Smoke Zone with its Break Glass Unit.
3.3.1 Configuration of local output
3.3.1.1 Configuration of error signal to the BMS
To start the configuration of the local output signal:
P
ress: “Configuration”
“(error down)”
“Local Output”
Select “S3, X4.1/2”
Set the “Output mode” to “Binary output”
Set the “Controlled by smoke zones” to “1”
Press the “Smoke zone output function” “…” and select “Any error”
The binary output will now become active (ON) when Smoke Zone 1 reports an error.