Faults, causes and remedies
en
Installation and operating instructions Wilo-Yonos GIGA2.0-I/-D
197
Code
Warning
Cause
Remedy
573
Communication to dis-
play and operating unit
interrupted.
Internal communica-
tion to display and
operating unit inter-
rupted.
Check the ribbon cable
connection.
Additional information about causes and remedies:
The display and operating unit is connected to the pump’s electronics on its
rear side via a ribbon cable.
574
Communication to CIF
module interrupted.
Internal communica-
tion to the CIF mod-
ule interrupted.
Check/clean contacts
between CIF module and
electronic module.
Additional information about causes and remedy:
The CIF module is connected to the pump in the terminal room via four con-
tacts.
578
Display and control unit
defective.
A fault in the display
and operating unit
has been identified.
Replace display and oper-
ating unit.
Additional information about causes and remedy:
The display and operating unit is available as a spare part.
582
Twin-head pump is not
compatible.
Twin-head pump
partner is not com-
patible with this
pump.
Select/install appropriate
twin-head pump partner.
Additional information about causes and remedy:
Twin-head pump function is only possible with two compatible pumps of the
same type.
586
Overvoltage
Power supply is too
high.
Check power supply
Additional information about causes and remedy:
The pump is running. If the voltage continues to increase, the pump is shut
down.
Excessive voltages can damage the pump.
588
Electronic fan blocked,
defective or not con-
nected.
Electronic fan does
not work
Check the fan cable.
1)
BMS = Building management system
NOTICE
The warning W573 “Communication to the display and control unit interrupted”, is
shown differently from all other warnings on the display.
Warning: W573
Communication between display
and electronic module interrupted
Please check user manual
Fig. 99:
Warning W573
Universal
Display text
Warning: W573
Warning W573
Communication
between display and
electronic module inter-
rupted Please check op-
erating manual
Please check operating
manual
Communication between display and electronic module in-
terrupted.
Please check in user manual.
Содержание Yonos GIGA2.0-D
Страница 2: ......
Страница 3: ...Fig I Yonos GIGA2 0 I D DN 32 DN 80 D E D...
Страница 4: ...Fig II Yonos GIGA2 0 I D DN 100 DN 125 D D E...
Страница 5: ...5 Deutsch 6 English 108 Fran ais 208 Nederlands 314...
Страница 416: ......
Страница 417: ......
Страница 418: ......
Страница 419: ......
Страница 420: ......
Страница 421: ......
Страница 422: ......
Страница 423: ......