en
Installation of CIF module
144
WILO SE 2022-05
Fig. 28:
Electronic module
The graphic display can be turned in 90° steps. To do this, open the upper part of the
electronic module using a screwdriver.
The graphic display is fixed in position by two snap-in hooks.
1.
Carefully open the snap-in hooks with a tool (e.g. screwdriver).
2.
Turn the graphic display to the desired position.
3.
Fix the graphic display with the snap-in hooks.
4.
Fit the upper part of the module again. Observe the screw tightening torques on
the electronic module.
Component
Fig./Item screw
(nut)
Thread
Tightening
torque
[Nm] ±10 %
(unless other-
wise stated)
Installa-
tion in-
formation
Electronic module
upper part
Fig. 28, Item 1
Fig. I, Item 2
M5
4.5
Threaded cable
gland union nut
Fig. 19, Item 1
M25
11
*
Threaded cable
gland
Fig. 19, Item 1
M25x1.5
8
*
Threaded cable
gland union nut
Fig. 19, Item 6
M20x1.5
6
*
Threaded cable
gland
Fig. 19, Item 6
M20x1.5
5
Power terminals and
control terminals
Fig. 20, 21
Pusher
Slot 0.6x3.5
**
Earthing screw
Fig. 20, Item 5
M5
4.5
CIF module
Fig. 28, Item 4
PT 30x10
0.9
Wilo-Connectivity
Interface cover
Fig. 1, Item 8
M3x10
0.6
Table 14:
Tightening torques for electronic module
*
Tighten when installing the cables.
**
Press with screwdriver to plug and unplug the cable.
8
Installation of CIF module
DANGER
Risk of fatal electrical shock!
Immediate risk of fatal injury if live components are touched!
• Check whether all connections are voltage-free!
CIF modules (accessories) are used for communication between pumps and building
management systems. CIF modules are attached in the electronic module (Fig. 28,
Item 4).
ƒ
For twin-head pumps, only the main pump must be equipped with a CIF module.
ƒ
For pumps in Y-pipe applications in which the electronic modules are connected to
each other through the Wilo Net, only the main pump also requires a CIF module.
NOTICE
When using CIF module Ethernet, the use of the accessory “Connection M12 RJ45
CIF-Ethernet” is recommended.
Required for easy disconnection of the data cable connection via the SPEEDCON
socket outside of the electronic module when maintenance of the pump is required.
Содержание Yonos GIGA2.0-D
Страница 2: ......
Страница 3: ...Fig I Yonos GIGA2 0 I D DN 32 DN 80 D E D...
Страница 4: ...Fig II Yonos GIGA2 0 I D DN 100 DN 125 D D E...
Страница 5: ...5 Deutsch 6 English 108 Fran ais 208 Nederlands 314...
Страница 416: ......
Страница 417: ......
Страница 418: ......
Страница 419: ......
Страница 420: ......
Страница 421: ......
Страница 422: ......
Страница 423: ......