Installation and operating instructions Wilo-EMUport FTS MG..., MS..., FG..., FS...
41
MAINTENANCE English
8.5.7. Checking the settings of the level controllers
The level controller is set correctly at the factory.
For the switching points set in the factory, please
see the relevant circuit diagram or system de-
scription.
Check the following:
• If the switching points are set correctly:
• At the OFF switching point, no air is sucked in
through the intake pipe. Otherwise, set the OFF
switching point higher.
• When pumping begins, the shut-off balls in the
solids separation tank do not strike against the
housing. Otherwise, set the ON switching point
higher.
• The sensors function error-free.
8.6. Releasing the system for operation
After maintenance, the system may only be
released for use in normal mode again after
a comprehensive test run has been performed.
During the test run the following must be
checked:
• No connections leak
• The pumps operate alternately
• The switching points of the level controller
are set correctly
•
Alarm messages (e.g. for excess backup)
are shown correctly
Содержание EMUport FTS FG Series
Страница 4: ...Fig 3 1 2 6 5 4 7 8 3...
Страница 6: ......
Страница 42: ......
Страница 62: ......
Страница 114: ......
Страница 116: ...116 WILO SE V4 1 DIN A4 1 1 1 1 2 2 1 3 1 4 1 4 1 1 5 1 6 1 7 1 8...
Страница 117: ...Wilo EMUport FTS MG MS FG FS 117 1 8 1 1 8 2 12 18 1 8 3 1 8 4 1 8 5 1 8 6 2 2 1 2 1 1...
Страница 118: ...118 WILO SE V4 1 DIN A4 2 1 2 DIN ANSI 2 2...
Страница 119: ...Wilo EMUport FTS MG MS FG FS 119 2 3 2 4 2 5 VDE 0100 2 6 RCD EVU 2 7...
Страница 120: ...120 WILO SE V4 1 DIN A4 2 8 2 9 2 10 2 11 70 90 85 A 3 3 1...
Страница 121: ...Wilo EMUport FTS MG MS FG FS 121 3 2 3 3 1 15 C 5 25 C 6 3 4 4...
Страница 124: ...124 WILO SE V4 1 DIN A4 5 1 ATV 5 30 C 5 2 FTS MG FG PE HD FTS MS FS 5 3 5 4 0 7 18 55 DN 100 5 5...
Страница 125: ...Wilo EMUport FTS MG MS FG FS 125 Wilo 5 5 1 MS FS 1 1 2 1 2 2 2 3 4 5 5 2 5 5 3...
Страница 126: ...126 WILO SE V4 1 DIN A4 5 5 4 5 5 5 1 5 6 RCD 5 6 1 5 6 2...
Страница 127: ...Wilo EMUport FTS MG MS FG FS 127 5 6 3 5 7 5 7 1 VDE 0660 RCD 5 7 2 5 7 3 6 6 1 VDE...
Страница 128: ...128 WILO SE V4 1 DIN A4 6 2 6 3 Fig 2 1 5 2 6 3 7 4 8 1 2 3 3 4 5 5 3 3 7 3 3 6 6 4 6 4 1 6 4 2 20 6 4 3...
Страница 129: ...Wilo EMUport FTS MG MS FG FS 129 6 5 MG MS 1 5 FG FS 5 0 3 6 6 600 6 6 1 6 6 2 6 7 5 2 5 1 7...
Страница 130: ...130 WILO SE V4 1 DIN A4 7 1 1 2 3 4 7 2 1 2 3 4 5 6 40 C 7 2 1 7 2 2...
Страница 131: ...Wilo EMUport FTS MG MS FG FS 131 7 3 7 4 7 4 1 75 439 5a 5b 7 4 2 TA 524 02 91 689 7 4 3 8 Wilo...
Страница 132: ...132 WILO SE V4 1 DIN A4 1 2 8 8 8 75 439 5a 5b TA 524 02 91 689 8 1 10 32 6 10 8 2 29 8 3...
Страница 133: ...Wilo EMUport FTS MG MS FG FS 133 8 4 DIN EN 12056 4 8 4 1 3 6 12 8 5 8 5 1 8 5 2 8 5 3 MG MS FG FS 8 5 4 8 5 5...
Страница 134: ...134 WILO SE V4 1 DIN A4 8 5 6 1 2 3 4 5 1 2 6 7 8 9 1 2 3 4 5 6 1 2 7 8 9...
Страница 135: ...Wilo EMUport FTS MG MS FG FS 135 10 11 8 5 7 8 6...
Страница 136: ......
Страница 155: ......