Installation and operating instructions Wilo DrainAlarm/-GSM
25
OPERATION AND FUNCTION
English
5.4.11. Display of operating readiness
The LEDs in the housing cover signal proper func-
tion as follows.
DrainAlarm
Symbol Colour
Description
Green
LED is lit up: Mains voltage is present,
battery is charging
DrainAlarm GSM
Symbol Colour
Description
Green
LED is lit up: Mains voltage is present,
battery is charging
Green
GSM module: LED is lit up
Ready for operation after 2 minutes
Yellow
GSM module: Status LED
Continuous flashing: Start procedure
Is lit up: Connected to the mains
Flashes twice: SIM card not available
6. Operation and function
This section contains all information on operating
the alarm switchgear and how it functions.
DANGER due to electrical voltage!
When working on the uncovered alarm
switchgear, there is a risk of fatal electric
shocks. Only operate the alarm switchgear
with the cover closed!
6.1. Controls
After successful mains connection, the alarm
switchgear operates fully autonomously. If an
alarm is signalled, only the acknowledgement
button must be pressed. The current operating
status is indicated via LEDs.
6.1.1. Buttons
Symbol
Description
off
Acknowledgement button
This button is used to acknowledge alarm signals:
the yellow LED goes out and the buzzer stops
6.1.2. LEDs
Symbol Colour
Description
Green
LED is lit up: Mains voltage is present,
battery is charging
Symbol Colour
Description
Red
Alarm signal:
LED is lit up: Signal present at terminal
6 and 7 or mains voltage missing
LED goes out as soon as the signal at
terminal 6 and 7 is no longer present
and the mains voltage is present again.
Yellow
Alarm signal:
LED is lit up in parallel to the red LED
LED goes out as soon as the alarm
signal was acknowledged.
Green
GSM module: LED is lit up
Ready for operation after 2 minutes
Yellow
GSM module: Status LED
Continuous flashing: Start procedure
Is lit up: Connected to the mains
Flashes once: Modem does not respond
Flashes twice: SIM card not available
Flashes three times: GSM signal too
weak
1
Green
GSM module: When the LED lights up,
the respective relay is connected
2
6.2.
Configuring the GSM module
After installation, the GSM module in the DrainAl-
arm GSM alarm switchgear must be configured via
software. For this purpose, the alarm switchgear
must be connected to the PC via a mini USB cable
and configured via software.
6.2.1. Mobile phone plan and SIM card
The alarm switchgear starts automatically
after the electrical connection is established. If
configuration is incorrect, text messages can be
sent automatically. This can result in high costs.
To avoid this, always comply with the following
points:
•
Do not insert the SIM card until the device has
been configured correctly and in full.
•
Choose an appropriate mobile phone plan with
transparent test message costs.
6.2.2. System requirements
Description
Minimum re-
quirement
Recommended
requirement
PC system
IBM compatible PC with x86 or x64
processor
RAM
256 MB
512 MB
Hard drive space
10 MB
10 MB
CD-ROM
Required for installation from CD
VGA
1024 x 768,
256 colours
1280 x 800
32 bit
USB standard*
2.0
2.0
USB connection
Mini-USB
Mini-USB