Manual V 1.03 / ref. no. 00.000.0059.0 / 28.03.2001
6.8.2 RESET
button
The RESET button is located on the front of the bus
coupler next to the 7-segment display. If you press it, a
RESET is triggered which resets the bus interface and
reinitialises the motor starter and any further
podis
motor control units that are connected via the extension
bus.
6.8.3
Diagnostics under PROFIBUS DP
The
podis
DRIVE
PROFIBUS interfaces support
extended diagnostics information in addition to the
standard 6 byte diagnostics information specified in the
norm. This data is in the form of device-related
diagnostics signals.
The bus coupler makes the PROFIBUS DP standard
diagnostics data available after a request from the master
or in the event of an error.
Byte Bit Short
code
Description
0
0
non_exist
Slave does not exist (sets
master)
1
station_not_ready
Slave is not ready for data
exchange
2 cfg_fault
Configuration
data
between
master and slave does not
match
3 ext_diag
Extended
diagnostics
bytes
exist
4
5
invalid_slave_response
Always set to 0 by slave
6 prm_fault
Fault
in
parameterisation
7
master_lock
Slave has been
parameterised by a master
1 0 prm_req
Slave
must
be
reassigned
parameters
1 stat_diag
Static
diagnostics
2
Always
1
3 wd_on
Response
monitoring
active
4
freeze_mode
Freeze command active
5 sync_mode
Sync
command
active
6
Reserved
7
slave_deactivated
1 if slave is deactivated by
master
2 0…6
Reserved
7
ext_diag_overflow
Master or slave has too
much diagnostics data
Byte Description
3
Master address according to parameterisation
4
ID number High Byte
5
ID number Low Byte
Standard diagnostics data