5.7
Wieland Electric | BA000349 | 05.2007
5 |
Commissioning
)
The programming system has now automatically assigned the I/O addresses for the pro-
grammed I/O modules.
In our example:
5.7 Parameter setting of the podisMOT properties
The STEP7 software menu item "Edit / Object Properties" allows entering an automatic param-
eter setting by the PROFIBUS master. These parameters allow configuring several properties
for operating the DP slave.
Select Response Monitoring.
Response Monitoring provides you with an option for the DP slave to respond to an error
from the DP master or to an interruption of the data traffic on the bus. If the DP slave is not
addressed within the planned response monitoring time, the DP slave switches to safe state
(all outputs set to "0" or substitute value output).
WARNING
If you deactivate the response monitoring, the outputs of the corresponding DP slave
may not be set to "0" in case of an error. For this reason, it is highly recommended to
deactivate the response monitoring only for commissioning.
"General" tab