background image

 

Technical Data

 

Power circuit 

min

 

typical

 

max

 

Operating voltage DC U

B

 

20.4 V DC

 

24 V DC

 

26.4 V DC

 Rated 

power

 

 

2.8 W

 

 Residual 

ripple 

U

SS

 

 

 

2.4 V

 Inrush 

current, 

peak

 

5 A

 

 

Operating voltage AC U

B

 

95 V AC

 

115-230 V AC

 

253 V AC

 Rated 

power

 

 

3.2 W / 6.3 VA

 

 Nominal 

frequency

 

48 Hz

 

50-60 Hz

 

62 Hz

 Inrush 

current, 

peak

 

5 A

 

 

Fuse, internal

 

 

T 2 A

 

Isolation between supply circuit / control circuit

 

 

yes (AC 115 - 230 V) 

Control circuit  

Rated output voltage (S11 to S21), short-circuit protected

 

 

22 V

 

40 V

Inputs (S12/S22, S32, S14, S34, Y2, Y40)

 

 

 

U

e

, High

 

15 V

 

24 V

 

30 V

U

e

, Low

 

-5 V

 

0 V

 

5 V

I

e

, High

 

 

3 mA

 

4.5 mA

I

e

, Low

 

-2.5 mA

 

 

2.1 mA

Input capacity

 

 

10 nF

 

Line resistance

 

 

 

70 

Line capacity

 

 

 

200 nF

Times

 

 

 

OFF time t

R

 (K1, K2 and K5)

 

 

 

20 ms

Release delay time t

RV

 (K3, K4), tolerance

 

 

0.1 % 

±

15 ms

 

 

0.1 to 3 s

 

0.1 / 0.2 / 0.3 / 0.4 / 0.5 / 0.8 / 1.0 / 1.5 / 2.0 / 3.0 s

 

0.1 to 30 s

 

0.1 / 2 / 4 / 6 / 8 / 10 / 15 / 20 / 25 / 30 s 

 

0.1 to 300 s

 

0.1 / 20 / 40 / 60 / 80 / 100 / 150 / 200 / 250 / 300 s

Response time t

A

 

 

 

200 ms

Ready time t

B

 

300 ms

 

 

Minimum activation time t

M

 

100 ms

 

 

Recovery time t

W

 

50 ms

 

 

Discrepancy time t

D

 

 

1 s

 

permitted test pulse time t

TP

 

 

 

1 ms

permitted test frequency

 

 

 

10 s

-1

Output circuit 
Enabling paths

 

 

Contacts 

  SNV 

4074SL 

   SNV 

4076SL

 

2 NO and 2 NC contacts not delayed, 2 delayed NO and 2 NC contacts

3 NO and 1 NC contacts not delayed, 3 delayed NO contacts

Rated switching voltage U

n

 

230 V AC 

max / min current I

n

per current path

 

6 A / 5 mA (24V) 

 fuse

 

max. 6 A operating class gG (Use in combustion plant max 0.6 x I

n

)

max. total current of all current paths

 

See Diagram 1 

Utilisation category according to DIN EN 60947-5-1

 

AC-15: Ue 230 V, Ie 3 A 

DC-13: Ue 24 V, Ie 3 A 

Mechanical service life (switching mechanisms)

 

10x10

6

 

General data 

Air gap / creepage paths between the circuits 

 

according to DIN EN 60664-1 

Pollution degree / Rated surge voltage

 

III / 4 kV (Basic insulation) 

Rated voltage

 

300 V AC 

Contamination level of the device: inside / outside

 

2 / 3 

Protection class according to DIN EN 60529 Case / terminals

 

IP 40 / IP 20 

Ambient / storage temperature

 

-25 to +55 / -25 to +75 °C 

Weight

 

DC device

 

0.33 kg 

AC device

 

0.35 kg 

Terminals and connection data 

screw-type terminals

spring-type terminals

Single-core or finely stranded 

1 × 0.2–2.5 mm² / 2 × 0.2–1.0 mm²

1 × 0.2–1.5 mm²

Finely stranded with wire-end ferrule acc. to DIN 46228 

1 × 0.25–2.5 mm² / 2 × 0.25–1.0 mm²

1 × 0.25–1.5 mm² (trapezoid crimping)

AWG 26–14

24–16

Max. tightening torque 

0.5–0.6 Nm (5–7 lbf-in)

Stripping length 

max. 7 mm 

LED 

Colour 

View 

Meaning

SUPPLY

 

Green

 

On

 

Supply voltage present

 

Reset

 

Green

 

On 
Flashing 3 Hz

 

S14 on
S14 and S34 on

 

K1,K2

 

Green

 

On

 

Relays K1 and K2 (and K5) on

 

K3,K4

 

Green

 

On 
Flashing 1Hz

 

Relays K3 and K4 on
Release delay time active (only for t

RV

 > 3s)

 

FLT

 

Red

 

Flashing 3Hz 
On

 

Internal error (self-monitoring)
Different from release delay time 

Содержание NV 4074SL

Страница 1: ...ltelemente OSSD einer Lichtschranke oder anderer Sicher heitssensoren mit Halbleiter Ausg ngen k nnen verarbeitet werden Testpulse die tTP sind beeinflussen die Ger tefunktionen nicht Testpulse tTP k...

Страница 2: ...ber Sensoren Leitungen etc ist f r die h chste am Ger t anliegende Span nung auszulegen Bei Betrieb des Ger tes in der Betriebsart zweikanalig nicht querschlusssicher sind Ma nahmen vorzusehen die ein...

Страница 3: ...r und 2 ffner verz gert 3 Schlie er und 1 ffner unverz gert 3 Schlie er verz gert Schaltnennspannung Un AC 230 V max min Strom In pro Strompfad 6 A 5 mA 24 V Absicherung Max 6 A Betriebsklasse gG Eins...

Страница 4: ...eedback circuits the relays activate with the closing of the safety circuits see In stallation 5 OSSD compatible Output signal switching devices OSSD of a light barrier or other safety sensors with se...

Страница 5: ...lass of at least IP 54 In the case of operation of the device in two channel mode without crossover protection actions must be taken which prevent a crossover short circuit such as e g separated line...

Страница 6: ...ed 3 delayed NO contacts Rated switching voltage Un 230 V AC max min current In per current path 6 A 5 mA 24V fuse max 6 A operating class gG Use in combustion plant max 0 6 x In max total current of...

Страница 7: ...ur ferm es les relais sont activ s avec la fermeture des circuits de s curit voir Installation 5 Compatible OSSD Permet de traiter les l ments logiques de sortie OSSD d une barri re lumineuse ou d aut...

Страница 8: ...e de protection minimal d IP 54 En cas d utilisation du module en mode bi canal non prot g contre les courts circuits transversaux il faut pr voir des mesures emp chant un court circuit transversal co...

Страница 9: ...cts fermeture et 1 contact ouverture non temporis 3 contacts fermeture temporis s Tension nominale de commutation Un 230 V c a courant permanent max min In par trajet de courant 6 A 5 mA 24 V fusible...

Страница 10: ...lit OSSD possibile l elaborazione di dispositivi di commutazione del segnale di uscita OSSD di una fotocellula o di altri sensori di sicurezza con uscite a semiconduttore Impulsi di prova tTP non infl...

Страница 11: ...vi ecc deve essere realizzato per la tensione massima presente nell ap parecchio In caso di utilizzo dell apparecchio nella modalit bicanale senza protezione da cortocircuiti trasversali devono essere...

Страница 12: ...tura ritardati 3 contatti di chiusura e 1 contatto di apertura non ritardati 3 contatti di chiusura ritardati Tensione nominale di commutazione Un CA 230 V Corrente max min In per circuito 6 A 5 mA 24...

Страница 13: ...se los circuitos de seguridad v ase Instalaci n 5 Compatible con OSSD Se pueden procesar elementos de conmutaci n de se al de salida OSSD de una barrera fotoel ctrica o de otros sensores de seguridad...

Страница 14: ...arato En caso de que el aparato se utilice en el modo de funcionamiento de dos canales sin protecci n contra cortocircuitos transversales se deber n prever medidas que impidan que se produzca un corto...

Страница 15: ...3 NA con retardo Tensi n nominal de conmutaci n Un CA 230 V Corriente m x m n In por l nea de contactos 6 A 5 mA 24 V Fusible M x 6 A clase de servicio gG uso en instalaciones de combusti n m x 0 6 x...

Страница 16: ...z zamkni ciem si obwod w zabezpieczaj cych patrz instalacja 5 Kompatybilno OSSD Przetwarzane mog by elementy prze czaj ce wyj cia OSSD fotokom rki lub innych czujnik w zabezpieczaj cych z wyj ciami p...

Страница 17: ...y szego napi cia wyst puj cego w urz dzeniu Podczas eksploatacji urz dzenia w trybie dwukana owym bez zabezpieczenia krosowania nale y przewidzie pewne rodki jak np oddzielne prowadzenie przewod w oby...

Страница 18: ...e i 2 rozwierne z op nieniem 3 zestyki zwierne i 1 rozwierny bez op nienia 3 zestyki zwierne z op nieniem Znamionowe napi cie czeniowe Un AC 230 V maks min pr d In na cie k pr dow 6 A 5 mA 24 V Bezpie...

Страница 19: ...set manuell berwacht mit R ckf hrkreis Reset manually monitored with feedback circuit R initialisation contr le manuel avec boucle de retour 7 Time Clear Zeitablauf beenden Time Clear end delay time T...

Страница 20: ...einicio autom tico con bucle de realimentaci n Reset automatycznie z obwodem przywracania 6 Reset controllo manuale con circuito di retroazione Reinicio controlado manualmente con bucle de realimentac...

Страница 21: ...AC 115 230 V Diagramm 1 Diagram 1 Diagramme 1 I Summenstrom I total current I courant total DC Ger te dc device cc appareillage AC Ger te ac device ca appareillage Beispiel example exemble I13 14 2 A...

Страница 22: ...C AC 115 230 V Schema 1 Diagrama 1 Wykres 1 I corrente cumulativa I intensidad residual I pr d sumaryczny apparecchi CC aparatos CC Urz dzenia DC apparecchi CA aparatos CA Urz dzenia AC Esempio Ejempl...

Страница 23: ...Pfeilrichtung aus der Verrastung l sen und von der Hutschiene nehmen Release relay and remove it from the DIN rail see arrow D verrouillez le relais et retirez le du rail DIN voir la fl che Abmessung...

Страница 24: ...incastro in direzione della freccia e rimuoverlo dalla barra DIN Manteni ndolo apretado desencaje el rel y s quelo del carril DIN en el sentido de la flecha Wciskaj c przeka nik zwolni go z zatrzasku...

Отзывы: