Version 10.12.2019

 

page 6 

 

 WERAC Elektronik GmbH 

 
 
 
 
 
 
 
 
 
 

Fig.2: 

Diagram of connections for the external safety category 4 contacts 

 

Attention: 

In order to achieve the corresponding safety level, the external control of contact pairs 1 and 2 
must  also  be  carried  out  in  accordance  with  Performance  Level  PL  e,  Category  4  in 
accordance with EN ISO 13849-1. 
 

Proposed wiring diagrams for the sequential switching 

The contactors or relays actuated by the control unit must have positively driven contacts and 
be suitable for industrial use. 
IMPORTANT: When using plug-in auxiliary contacts, the positively driven operation must also 
be available between the main contact set. It must also be checked whether disconnection of 
the  auxiliary  block  is  detected  by  the  controller.  No  further  work  on  the  machine  may  be 
possible in such cases. 
The spark suppression must always be connected via the contactor coil (by means of an RC 
element or varistor). 
 
 

5.1 

Proposed wiring diagram for control unit WGN100, WGN 110 to Performance Level PL e, 
Category 4 according to EN ISO 13849-1 on power-driven machinery (PDM) with start-up 
test and restart lock 

 

The control line for contactor A (terminals A1, A2), contactor B (terminals A5, A6) and the test 
(T1,  T2)  must  be  laid  in  separate  cables  if  the  control  unit  and  the  contactors  are  spatially 
separated. if both are located in the control cabinet, standard wiring is adequate. The user has 
to provide a max. 2 A fuse for current-limiting measures to protect the output signal switching 
devices (OSSD). 
We will be pleased to supply you with other proposed wiring diagrams on inquiry. 
 
 
 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

0V 

+24V 

 max. 2A 

A1

 

T1

 

d

 

c

 

b

 

a

 

d

 

c

 

b

 

a

 

A2

 

A6

 

T2

 

WGN 100 
WGN 110 

reserve 

 

b

 

d

 

a

 

c

 

 m

a

x.

 2

A

 

b

 

d

 

a

 

c

 

 

 m

a

x.

 2

A

 

b

 

d

 

a

 

c

 

 m

a

x.

 2

A

 

d

 

c

 

b

 

a

 

A4

 

A3

 

A7

 

A5

 

Fig. 3: 

Proposed wiring diagrams for the sequential switching 

Start enable 10-50V

 

 

0V

 

 

24V

 

mains

 

outputs 

24V

 

AC or DC

 

T1

 

T2

 

transmitter 

 

receiver 

 

 

RJ 45

 

 

RJ 45

 

control unit WGN 110 

 

A2

 

A3

 

A4

 

A1

 

A7

 

A5

 

A6

 

B2

 

B3

 

B4

 

B1

 

B7

 

B5

 

B6

 

B8

 

Input contact pair 1 

Safety category 4 

Input contact pair 2 

Safety category 4 

Содержание SAFETY 40

Страница 1: ...Version 10 12 2019 Safety Light Grids and Multibeam Safety Light Barriers Technical Description...

Страница 2: ...L e safety category 4 of EN ISO 13849 1 2008 resolution 14 mm finger guard 30 mm finger guard or 40 mm hand guard Width of guarded area with resolution 30 mm or 40 mm 0 6 m or 3 10 m with 14 mm resolu...

Страница 3: ...n the control unit and visually indicated for the user in the emitter The light grid is in the OFF state after power supply ON or a light barrier interruption This is indicated by the red LED Provided...

Страница 4: ...100 see fig 1 connection A1 A2 normally open contact security output relay A OSSD 1 connection A5 A6 normally open contact security output relay B OSSD 2 connection A3 A4 normally closed contact e g m...

Страница 5: ...unit to emitter or receiver 10 m with UL listed cables 15 m with VDE 0472 804 cables Table 4 4 Diagram of connections The sequential switching has to conform the risk evaluation of the machinery Our...

Страница 6: ...r varistor 5 1 Proposed wiring diagram for control unit WGN100 WGN 110 to Performance Level PL e Category 4 according to EN ISO 13849 1 on power driven machinery PDM with start up test and restart loc...

Страница 7: ...d EN 999 ISO 13855 and the type C standards of the corresponding machinery Operation e g in the following areas of operation is possible Operating machines for the chemicals rubber and plastics indust...

Страница 8: ...m Example A machine with a braking time of 100 ms is equipped with a light grid ESPE with a resolution of 30 mm and a response time of 20 ms C 8 30 14 mm 128 mm S 2 m s 100 ms 20 ms 128 mm 240 mm 128...

Страница 9: ...s of 1 2 or 3 passive components green If the result of the risk evaluation is such that protective devices have to be used with several single beams they must be positioned at a distance obtained usi...

Страница 10: ...label on the emitters and receivers In the case of cascades the response time is dependent on the total number of lines in all light grids The following applies tR cascade tRG tRL total It is not val...

Страница 11: ...of 1 or max 2 deflector mirrors 6 8 Optical bypassing To prevent optical bypassing a minimum distance A of the optical axis to reflective surfaces must be complied with Read off the value in the diagr...

Страница 12: ...vers The procedure for alignment of the emitter and receiver elements is described in the following section a The emitters and receivers are mounted as described under 6 9 Ensure that the longitudinal...

Страница 13: ...rupted off grid ready for activation external restart lock enabled off grid ready for activation Less light reserve in relation to calibrated reference off light grid active and free Less light reserv...

Страница 14: ...light grid LG If an operating mode with bypassing the light grid was selected in the alignment mode the safety function of the light grid can be bypassed with contact pair 1 and 2 in mode 1 and 3 byp...

Страница 15: ...green OSSD ON as soon as the start release is activated and the light grid is free 7 In normal operation in mode 1 the DIP switch is set In mode 2 as AOPD with additional function reduced resolution...

Страница 16: ...be open Both contacts of a contact pair must close within a time slot of one second Only the contact pair which fulfills this requirement activates the overriding The second contact pair now cannot i...

Страница 17: ...t the switches Caution risk of injury When using the function reduced resolution the lines specified for bypassing were no longer evaluated when contact pair 1 is closed The guarded area then is reduc...

Страница 18: ...SichV nature scope and times for regular inspections must be determined by the user for the specific work equipment Furthermore the qualifications and requirements e g technical expert or professional...

Страница 19: ...ion code for standard light grid with 14 30 and 40 mm resolution W G x x x x x x x x x 0 Examples for emitters standard design with 14 mm resolution System length Type designation code Overall length...

Страница 20: ...4 1 ms 208 2 mm results at a 14 mm resolution see Section 6 2 and S230 336 2 mm at a 30 mm resolution The dimension for the height of the section with a 14 mm resolution is calculated as follows mm 26...

Страница 21: ...mm No of lines NL Response time tR in ms 1085 WLS 4108A 080 0 1123 1200 80 15 18 3 1080 WLS 4108A 100 0 1118 1200 100 12 17 8 1070 WLS 4107A 120 0 1108 1200 120 10 17 5 760 WLS 4076A 150 0 798 900 150...

Страница 22: ...listing Depending on the mounting type for rail mounting number of retainer blocks WHK1 number of angle brackets WHW1 or number of hinge brackets WSH1 for end piece mounting number of mounting bracke...

Страница 23: ...00 2 Fig 15 Control unit WGN 110 0 168 DIP S1 115 7 Aufschnappteil f r TS 35 45 132 Empf Sender Start Ausg nge Netz gr n gelb rot RJ 45 RJ 45 Typenschild 10 20 16 168 DIP S1 115 7 Aufschnappteil f r T...

Страница 24: ...AC Elektronik GmbH Fig 16 Retainer block WHK1 Left Fig 17 Angle bracket WHW1 for fixing the retainer block Right Fig 18 Mounting bracket WHW2 for fixing the head pieces Fig 19 Hinge bracket WSH1 10 22...

Страница 25: ...Emitter 30 mm resolution with 2 lenses per 50 mm module The 14 mm resolution has 5 lenses per 50 mm module Resolution 40 mm has one lense per 35 mm module In the case of cascading the connection on th...

Отзывы: