background image

Version 10.12.2019

 

page 16 

 

 WERAC Elektronik GmbH 

10. After  activating  the  reduced  resolution  function  with  contact  pair  1,  the  test  rod  must  be 

used  to  test  whether  the  taught-in  lines  to  be  blanked  correspond  to  the  desired  ones.  If 
not, the complete teach-in procedure must be repeated until the configuration is correct. 

11. In normal operation in mode 1, the DIP switch is set: 
 
In mode 3 as AOPD with additional function fixed blanking and bypassing: 
1.  device in OFF state (supply voltage off) 
2.  set DIP switch S1-1 to the following position: 
 
3.  the areas to be permanently blanked must be interrupted or covered. Caution: At least one 

line must remain free. 

4.  switch on the device 
5.  swivel  the  light  grid  over  the  entire  reception  area  and  align  it  centrally.  The  yellow  LED 

lights  up.  Now  wait  30  seconds. Within  this  time  the  lines  to  be  blanked  are  defined  and 
saved. 

6.  Switch off dip S1-1. 
 
7.  After a pause of 5-7s (to remove the hand from the protected area, this is indicated by the 

flickering  red  LED),  the  control  unit  saves  the  mode,  the  lines  to  be  blanked  and  the 
reference  values  of  the  individual  lines  in  the  read-only  memory.  When  this  process  is 
completed, the red LED starts flashing. To exit the adjustment mode, the power supply and 
then DIP S1-2 must be switched off. 

 

After the power supply is switched on again, the light grid goes into waiting mode (red and 
yellow  LEDs  light  up).  It  switches  to  green  (OSSD  =  ON)  as  soon  as  the  start  release  is 
activated and the light grid is free. 

8.  The guarded area must be tested in accordance with the given specifications. 
9.  In normal operation in mode 1, the DIP switch is set: 
 

6.11.6  Activate the bypass function of the light grid 

To  activate  the  bypassing  function  of  the  light  grid  system  in  safety  mode  1,  2  or  3  the 
following sequence must be met: 
Before a bypassing can be chosen and activated all contacts of the two type-4 contact pairs 
must  be  open.  Both  contacts  of  a  contact  pair  must  close  within  a  time  slot  of  one  second. 
Only  the  contact  pair  which  fulfills  this  requirement  activates  the  overriding.  The  second 
contact  pair  now  cannot  influence  the  bypassing  but  it  is  constantly  checked  if  the  contacts 
also  close  within  one  second.  If  the  time  slot  is  exceeded,  both  contacts  of  the  contact  pair 
must open again. As soon as one contact of the active contact pair opens, it is checked if the 
second  contact  pair  was  closed  correctly  and  a  bypassing  is  requested.  If  so  the  bypassing 
mode  is  passed  to  the  other  contact  pair,  if  not  the  overriding  is  stopped  and  the  light  grid 
guarantees the safety function. 
The bypassing mode can be activated and deactivated both in OSSD off mode (when the light 
grid is interrupted) and in normal mode when the light grid is unobstructed. 
 

Caution, risk of injury

 

Particularly  when  using  the  bypassing  in  OSSD  off  mode  it  must  be  ensured  by  measures 
defined through a risk assessment that an activation of the bypassing will cause no hazardous 
situation. 
I.e. only when hazards can be excluded by using other measures, e.g. a locked and monitored 
rolling door and a restart lock, the use of the overriding mode is permitted.  
 

6.11.7  Activate the reduced resolution mode 

6.11.7.1 In normal mode 

To  activate  the  reduced  resolution  function  of  the  light  grid  system  in  safety  mode  2  the 
following sequence must be met:  
Before switched blanking can be chosen and activated both contacts of the type-4 contact pair 
1 must be open. Both contacts of a contact pair must close within a time slot of one second. 
Only if the contact pair fulfills this requirement reduced resolution is activated. 
The second contact pair is constantly checked if the contacts also close within one second. If 
so the system switches to the bypassing mode. This takes place because the overriding has a 
higher  priority  than  the  reduced  resolution  mode.  I.e.  if  both  contact  pairs  close  correctly 

Dip S1 

on 

off 

1   

 

2   

 

3   

 

4   

 

5   6 

Dip S1 

on 

off 

1   

 

2   

 

3   

 

4   

 

5   6 

Dip S1 

on 

off 

1   

 

2   

 

3   

 

4   

 

5   6 

Dip S1 

on 

off 

1   

 

2   

 

3   

 

4   

 

5   6 

Dip S1 

on 

off 

1   

 

2   

 

3   

 

4   

 

5   6 

Содержание SAFETY 40

Страница 1: ...Version 10 12 2019 Safety Light Grids and Multibeam Safety Light Barriers Technical Description...

Страница 2: ...L e safety category 4 of EN ISO 13849 1 2008 resolution 14 mm finger guard 30 mm finger guard or 40 mm hand guard Width of guarded area with resolution 30 mm or 40 mm 0 6 m or 3 10 m with 14 mm resolu...

Страница 3: ...n the control unit and visually indicated for the user in the emitter The light grid is in the OFF state after power supply ON or a light barrier interruption This is indicated by the red LED Provided...

Страница 4: ...100 see fig 1 connection A1 A2 normally open contact security output relay A OSSD 1 connection A5 A6 normally open contact security output relay B OSSD 2 connection A3 A4 normally closed contact e g m...

Страница 5: ...unit to emitter or receiver 10 m with UL listed cables 15 m with VDE 0472 804 cables Table 4 4 Diagram of connections The sequential switching has to conform the risk evaluation of the machinery Our...

Страница 6: ...r varistor 5 1 Proposed wiring diagram for control unit WGN100 WGN 110 to Performance Level PL e Category 4 according to EN ISO 13849 1 on power driven machinery PDM with start up test and restart loc...

Страница 7: ...d EN 999 ISO 13855 and the type C standards of the corresponding machinery Operation e g in the following areas of operation is possible Operating machines for the chemicals rubber and plastics indust...

Страница 8: ...m Example A machine with a braking time of 100 ms is equipped with a light grid ESPE with a resolution of 30 mm and a response time of 20 ms C 8 30 14 mm 128 mm S 2 m s 100 ms 20 ms 128 mm 240 mm 128...

Страница 9: ...s of 1 2 or 3 passive components green If the result of the risk evaluation is such that protective devices have to be used with several single beams they must be positioned at a distance obtained usi...

Страница 10: ...label on the emitters and receivers In the case of cascades the response time is dependent on the total number of lines in all light grids The following applies tR cascade tRG tRL total It is not val...

Страница 11: ...of 1 or max 2 deflector mirrors 6 8 Optical bypassing To prevent optical bypassing a minimum distance A of the optical axis to reflective surfaces must be complied with Read off the value in the diagr...

Страница 12: ...vers The procedure for alignment of the emitter and receiver elements is described in the following section a The emitters and receivers are mounted as described under 6 9 Ensure that the longitudinal...

Страница 13: ...rupted off grid ready for activation external restart lock enabled off grid ready for activation Less light reserve in relation to calibrated reference off light grid active and free Less light reserv...

Страница 14: ...light grid LG If an operating mode with bypassing the light grid was selected in the alignment mode the safety function of the light grid can be bypassed with contact pair 1 and 2 in mode 1 and 3 byp...

Страница 15: ...green OSSD ON as soon as the start release is activated and the light grid is free 7 In normal operation in mode 1 the DIP switch is set In mode 2 as AOPD with additional function reduced resolution...

Страница 16: ...be open Both contacts of a contact pair must close within a time slot of one second Only the contact pair which fulfills this requirement activates the overriding The second contact pair now cannot i...

Страница 17: ...t the switches Caution risk of injury When using the function reduced resolution the lines specified for bypassing were no longer evaluated when contact pair 1 is closed The guarded area then is reduc...

Страница 18: ...SichV nature scope and times for regular inspections must be determined by the user for the specific work equipment Furthermore the qualifications and requirements e g technical expert or professional...

Страница 19: ...ion code for standard light grid with 14 30 and 40 mm resolution W G x x x x x x x x x 0 Examples for emitters standard design with 14 mm resolution System length Type designation code Overall length...

Страница 20: ...4 1 ms 208 2 mm results at a 14 mm resolution see Section 6 2 and S230 336 2 mm at a 30 mm resolution The dimension for the height of the section with a 14 mm resolution is calculated as follows mm 26...

Страница 21: ...mm No of lines NL Response time tR in ms 1085 WLS 4108A 080 0 1123 1200 80 15 18 3 1080 WLS 4108A 100 0 1118 1200 100 12 17 8 1070 WLS 4107A 120 0 1108 1200 120 10 17 5 760 WLS 4076A 150 0 798 900 150...

Страница 22: ...listing Depending on the mounting type for rail mounting number of retainer blocks WHK1 number of angle brackets WHW1 or number of hinge brackets WSH1 for end piece mounting number of mounting bracke...

Страница 23: ...00 2 Fig 15 Control unit WGN 110 0 168 DIP S1 115 7 Aufschnappteil f r TS 35 45 132 Empf Sender Start Ausg nge Netz gr n gelb rot RJ 45 RJ 45 Typenschild 10 20 16 168 DIP S1 115 7 Aufschnappteil f r T...

Страница 24: ...AC Elektronik GmbH Fig 16 Retainer block WHK1 Left Fig 17 Angle bracket WHW1 for fixing the retainer block Right Fig 18 Mounting bracket WHW2 for fixing the head pieces Fig 19 Hinge bracket WSH1 10 22...

Страница 25: ...Emitter 30 mm resolution with 2 lenses per 50 mm module The 14 mm resolution has 5 lenses per 50 mm module Resolution 40 mm has one lense per 35 mm module In the case of cascading the connection on th...

Отзывы: