17
Analog
Settings of the analog output
Mode U/I
Teach-In
At 0 V
At 10 V
At 4 mA
At 20 mA
Mode U/I: Analog output as current or voltage output. The analog output can be set up
as either a current or a voltage output by pressing the
U or the I key. The cor-
responding symbol is displayed.
Teach-In: Teach in the distances which correspond to the upper and lower voltage
values. The momentary actual distance is assigned to a voltage value of
10 V or a current value of 20 mA by pressing the 10 V or the 20 mA key.The
momentary actual distance is assigned to a voltage value of
0 V or a current
value of
4 mA by pressing the 0 V or the 4 mA key. If necessary, the assigned
distances can be readjusted with the help of menu items At
0 V or at 10 V.
At 0 V:
Distance at 0 V (visible in U mode) The distance assigned to the value 0 V
can be recalibrated by pressing the “+” key or the “–” key.
At 10 V: Distance at 10 V (visible in U mode) The distance assigned to the value 10 V
can be recalibrated by pressing the “+” key or the “–” key.
At 4 mA: Distance at 4 mA (visible in I mode) The distance assigned to the value 4 mA
can be recalibrated by pressing the “+” key or the “–” key.
At 20 mA: Distance at 20 mA (visible in I mode) The distance assigned to the value
20 mA can be recalibrated by pressing the “+” key or the “–” key.