Part number 550-100-305/0118
99
AquaBalance
TM
W
ALL
M
OUNT
GAS
-
FIRED
WATER
BOILER
—
Boiler Manual
Table 5
AquaBalance
™
list of System parameters (default settings)
System Parameters list (default settings)
There are 4 basic configurations within the DHW mode, selected by parameter DHW configuration (see Parameters list, Num.
1). Default value is 1 and it represents configuration 1. By changing DHW configuration (see Parameters list, Num. 1), all the data
will be automatically set at default condition. Parameters that will be changed according to the DHW mode are numbered from 9
to 46 (see Parameters list). All the parameters can be accessed with a communication package running on the PC. Some param-
eters are available by the installer TSP mode on the MMI or by the OT Room unit.
Category
E2 prom parameters
Unit
Range
Def
Description
Num.
Address
Description
Low
High
Value
DHW boiler type
1
CL5 – 05C8
]{!`"^\]
Num
1
4
3
System
2
ML – 80D0
\#^#^"^J`$"!
Num
0
1
0
End user setting
3
ML – 80E2
Summer / Winter selection
Num
0
1
1
End user setting
4
ML – 80E3
Economy / Comfort selection
Num
0
1
0
End user setting
5
CL5 – 0A9D
CH set point limit - HIGH
°F
68
194
190
End user setting
6
CL5 – 056D
CH user set point
°F
68
194
158
Exhaust protection
7
CL5 – 050B
Maximum exhaust gases temperature
°F
32
255
185
Firmware version
8
ML – 80E8
Firmware version
Num
0
99
03
]{!
9,1
CL5 – 066E
DHW P factor
Num
0
255
15
]{!
10,1
CL5 – 0691
DHW I factor
Num
0
255
240
]{!
11,1
ML – 80EB
DHW FF factor
Num
0
255
0
]{!
12,1
ML – 80EC
Fan absolute DHW maximum speed
Hz
0
220
200
]{!
13,1
ML – 80ED
Fan absolute CH maximum speed
Hz
0
220
200
]{!
14,1
ML – 80EE
Fan absolute minimum speed
Hz
0
165
40
]{!
15,1
CL5 – 2D89
Fan offset low level
Hz
0
220
10
]{!
16,1
ML – 80F0
Ignition level
%
0
100
60
]{!
17,1
ML – 80F1
DHW maximum output boost/limit level
%
75
125
100
]{!
18,1
ML – 80F2
DHW maximum output boost/limit time
Sec
0
120
60
]{!
19,1
ML – 80F3
XJ^XZ `]XJ{X
°F
68
194
167
]{!
20,1
ML – 80F4
XJ^XZ `]X?J{X
°F
68
194
163
]{!
21,1
ML – 80F5
DHW over-temp_burnerOFF – setpoint
°F
0
200
9
]{!
22,1
ML – 80F6
DHW over-temp_burnerON – setpoint
°F
0
200
0
]{!
23,1
ML – 80F7
DHW over-temp_burnerOFF – solar
°F
0
200
18
]{!
24,1
ML – 80F8
DHW over-temp_burnerON – solar
°F
0
200
18
]{!
25,1
ML – 80F9
DHW start waiting time – solar1
Sec
0
255
5
]{!
26,1
ML – 80FA
DHW start waiting time – solar2
Sec
0
255
10
]{!
27,1
ML – 80FB
DHW start waiting time – solar3
Sec
0
255
20
]{!
28,1
CL5 – 0A5E
DHW comfort switch on point
°F
0
176
104
]{!
29,1
CL5 – 0A62
DHW comfort on time
Sec
0
104
15
]{!
30,1
ML – 80FE
DHW comfort off time1
Min
0
255
20
]{!
31,1
ML – 80FF
DHW comfort off time2
Min
0
255
42
]{!
32,1
CL5 – 05A1
DHW OFF time
Sec
30
255
120
]{!
33,1
CL5 - 0A04
DHW pump over-run time
Sec
0
255
3
]{!
34,1
CL5 – 0A6D
Delta T1
°F
0
108
32
]{!
35,1
CL5 – 0A92
Delta T2
°F
0
255
63
Figure 127
Troubleshooting suggestions for
AquaBalance
™
boilers —
Fault displays and diagnostics
(continued)
34
Troubleshooting
(continued)