Part number 550-100-305/0118
100
AquaBalance
TM
W
ALL
M
OUNT
GAS
-
FIRED
WATER
BOILER
—
Boiler Manual
Category
E2 prom parameters
Unit
Range
Def
Description
Num.
Address
Description
Low
High
Value
]{!
36,1
ML – 8104
CH supply for CH pump over-run OFF
°F
32
212
122
]{!
37,1
CL5 – 0C94
CH supply for CH pump over-run ON
°F
0
200
18
]{!
38,1
ML – 8106
CH supply over-temp_burnerOFF
°F
0
212
203
]{!
39,1
ML – 8107
CH supply over-temp_burnerON
°F
32
212
194
]{!
40,1
ML – 8108
CH return over-temp_burnerOFF
°F
32
212
203
]{!
41,1
ML – 8109
CH return over-temp_burnerON
°F
32
212
194
]{!
42,1
ML – 810A
DHW set point limit – LOW
°F
50
104
104
]{!
43,1
CL5 – 1E76
DHW set point limit – HIGH
°F
104
158
131
]{!
44,1
CL5 – 05F4
DHW user set point – Default value
°F
50
158
131
]{!
45,1
ML – 810D
CH pre-pump time
Sec
0
60
30
]{!
46,1
ML – 810E
Minimum virtual set point
°F
68
176
95
]{!|
9,2
CL5 – 066E
DHW P factor
Num
0
255
5
]{!|
10,2
CL5 – 0691
DHW I factor
Num
0
255
240
]{!|
11,2
ML – 80EB
DHW FF factor
Num
0
255
0
]{!|
12,2
ML – 80EC
Fan absolute DHW maximum speed
Hz
0
220
200
]{!|
13,2
ML – 80ED
Fan absolute CH maximum speed
Hz
0
220
200
]{!|
14,2
ML – 80EE
Fan absolute minimum speed
Hz
0
165
40
]{!|
15,2
CL5 – 2D89
Fan offset low level
Hz
0
220
10
]{!|
16,2
ML – 80F0
Ignition level
%
0
100
60
]{!|
17,2
Free - TBD
]{!|
18,2
Free - TBD
]{!|
19,2
Free - TBD
]{!|
20,2
Free - TBD
]{!|
21,2
Free
-
TBD
]{!|
22,2
Free
-
TBD
]{!|
23,2
Free
-
TBD
]{!|
24,2
Free
-
TBD
]{!|
25,2
Free
-
TBD
]{!|
26,2
ML – 80FA
DHW pre-pump time
Sec
0
30
30
]{!|
27,2
ML – 80FB
Legionella protection
Num
0
7
0
]{!|
28,2
CL5 – 0A5E
DHW comfort hysteresis
°F
0
176
4
]{!|
29,2
CL5 – 0A62
DHW comfort temp difference
°F
0
104
0
]{!|
30,2
ML – 80FE
DHW pump start temperature
°F
0
255
32
]{!|
31,2
ML – 80FF
DHW pump start waiting time
Sec
0
255
0
]{!|
32,2
CL5 – 05A1
DHW OFF time
Sec
30
255
120
]{!|
33,2
CL5 – 0A04
DHW pump over-run time
Sec
0
255
30
]{!|
34,2
CL5 – 0A6D
Delta T1
°F
0
108
32
]{!|
35,2
CL5 – 0A92
Delta T2
°F
0
255
63
]{!|
36,2
ML – 8104
CH supply for CH pump over-run OFF
°F
32
212
68
]{!|
37,2
CL5 – 0C94
CH supply for CH pump over-run ON
°F
0
200
9
]{!|
38,2
ML – 8106
CH supply over-temp_burnerOFF
°F
0
212
9
]{!|
39,2
ML – 8107
CH supply over-temp_burnerON
°F
32
212
176
]{!|
40,2
ML – 8108
CH return over-temp_burnerOFF
°F
32
212
203
]{!|
41,2
ML – 8109
CH return over-temp_burnerON
°F
32
212
194
Figure 128
Troubleshooting suggestions for
AquaBalance
™
boilers —
Fault displays and diagnostics
(continued)
34
Troubleshooting
(continued)