WECO 5K3 LV/HV
36
2.5.1.2
LED Bar Indications
The LED bar is located on the front of the battery and is to be used as a visual indication.
After any major event that causes the BMS safety intervention, the BMS logic will allow four reconnections attempts:
The first after 4 minutes if the same condition occurs again the next three attempts will be every 4 hours.
Warning Indicator ( Most of the time switched off)
SOC 81-100%
SOC 31-80%
SOC 6-30%
SOC< 5%
1-
LED BAR Check. All the Blue LED will blink for 5 seconds
2-
SOC Green LED will appear to indicate actual SOC
1-
If the temperature rises above the BMS limits, the contactor opens
2-
The LED BAR will start blinking in red color
Warning Indicator
SOC 81-100%
SOC 31-80%
SOC 6-30%
SOC< 5%
1-
During the firmware upgrade the first blue LED is active for the entire upgrade
process
2-
When the upgrade process has been completed the LED BAR will turn to normal
START UP
FIRMWARE UPGRADE
OVER/UNDER TEMPERATURE
1-
If the voltage difference between modules is above 2V, all LED in
orange color
Warning Indicator
SOC 81-100%
SOC 31-80%
SOC 6-30%
SOC< 5%
1-
Wrong Voltage reading or any abnormal reading
2-
All the LED BARS will remain fixed red color
3-
The warning indicator will blink in RED color every 0.5 Sec
4-
The SOC indicator Is not displayed
1-
If the current exceed the BMS limit
2-
If the voltage exceeds the BMS limits (High or Low)
3-
The full LED bar blinks in RED Color
4-
The SOC Indicator is not displayed