November 2008
Part No. 920559 Rev H
4.8 Resetting After All Stop
This section applies to models connected to a Wayne Control system. Pressing the All Stop key on the 2400 MCS or
Wayne Plus or Nucleus sends a signal to the dispenser computer to interrupt product flow. To resume product flow:
•
2400 MCS -
All of the
unpaid/stopped
indicators will be illuminated on the 2400 MCS console. Press Clear until
the console display is totally blank. Press Pump Start. At this point all
unpaid/stopped
indicators will go out and
fuel flow may resume.
•
Wayne Plus
- All fueling point numbers will be shown in reverse index (light fueling point numbers on a dark
background) on the Wayne Plus. Press 0, Pump #, and Pump Start. At this point all operational fueling points will
be shown in normal format (dark fueling point numbers on a light background) and fuel flow may resume.
•
NUCLEUS -
All fueling point numbers will be shown with the STOP sign. Press the ALL START key. At this
point all the fueling points will show the gas pump icon and all or each can be authorized.
4.9 Stand-alone Operation
Note: All nozzles must be hung up before performing the following procedure.
The dispenser may be placed in stand-alone operation - not operated by a control system. To set the dispenser in stand-
alone, the correct function and its corresponding sub-function must be accessed. Next, the filling mode is changed to
its new setting and the data is saved. To access the desired sub-function, the following steps must be performed using
the remote control.
Bold
type denote remote control function and
italicized
type represents dispenser response. NOTE:
See additional requirements for standalone operation in Appendix C.
Accessing the filling mode Sub-function.
1. Press
ENTER
PASS 1
(enter password)
2. Press
ENTER
PASS 2
(enter password)
3. Press
ENTER.
The unit price display will show
F—
, indicating that it needs a function number to proceed)
4. Press
01
to access
F01
5. Press
ENTER.
The unit price display will show
F01,
indicating that the function has been accessed)
6. Press
ENTER
to access the sub-functions of
F01.
The unit price display will show
1.01
and the volume display will show a
1
indicating that the dispenser is in serial filling or that the dispenser is being controlled by the site controller via serial link.
7. Press
UP
to increment the value of function
1.02
by unity, followed by
ENTER
,
or press
#
and type
2
followed by
ENTER
(here
2
means that the filling mode is Stand-alone Mode, dispenser not supervised by site controller)
Saving the new setting
1. Press
ENTER.
The price display will show “–
– – – – –
“, the volume display will be blank and the unit price display will show
the last sub-function accessed.
2. Press
00
(to access
F00
)
3. Press
ENTER.
The unit price should now display
F00
, the price display will show “–
– – – – –
“ and the volume
display will be blank.
4. Press
ENTER
and the volume display will show a
1
.
5. Press
UP
twice to change the value in the volume display from
1
to
3.
6. Press
ENTER.
The volume display should show a
3
.
7. Press
ENTER
8.
CHANGE STORED
should appear on the display momentarily. The display returns to normal in a few seconds.
Содержание Ovation
Страница 1: ...INSTALLATION Ovation Dispensers OPERATION...
Страница 3: ...November 2008 Part No 920559 Rev H Ovation Series Dispensers Installation Operation...
Страница 4: ...November 2008 Part No 920559 Rev H...
Страница 54: ...48 Part No 920559 Rev H November 2008...
Страница 66: ...60 Part No 920559 Rev H November 2008...
Страница 67: ...61 November 2008 Part No 920559 Rev H DISTANCE BETWEEN EYE BOLTS 33 1...
Страница 68: ...62 Part No 920559 Rev H November 2008 INSTALLATION INSTRUCTION page 1 of 2 OVATION MODEL R13...
Страница 69: ...63 November 2008 Part No 920559 Rev H INSTALLATION INSTRUCTION page 2 of 2 OVATION MODEL R13...
Страница 70: ...64 Part No 920559 Rev H November 2008 INSTALLATION INSTRUCTION page 1 of 2 OVATION MODEL B23...
Страница 71: ...65 November 2008 Part No 920559 Rev H INSTALLATION INSTRUCTION page 2 of 2 OVATION MODEL B23...
Страница 72: ...66 Part No 920559 Rev H November 2008 INSTALLATION INSTRUCTION page 1 of 2 OVATION MODELS B12 AND R22...
Страница 73: ...67 November 2008 Part No 920559 Rev H INSTALLATION INSTRUCTION page 2 of 2 OVATION MODELS B12 AND R22...
Страница 74: ...68 Part No 920559 Rev H November 2008 INSTALLATION INSTRUCTION page 1 of 2 OVATION MODEL R11...
Страница 75: ...69 November 2008 Part No 920559 Rev H INSTALLATION INSTRUCTION page 2 of 2 OVATION MODEL R11...
Страница 76: ...70 November 2008 Part No 920559 Rev H...
Страница 77: ...71 November 2008 Part No 920559 Rev H 2 7151 C TYPICAL SITE WIRING...
Страница 78: ...72 Part No 920559 Rev H November 2008...
Страница 80: ...74 Part No 920559 Rev H November 2008...
Страница 81: ...75 November 2008 Part No 920559 Rev H APPENDIX D SITE INTERCONNECTION DIAGRAMS...
Страница 82: ...76 Part No 920559 Rev H November 2008 Figure D 1 Backroom Installation Wayne Control System...
Страница 84: ...78 Part No 920559 Rev H November 2008 Figure D 3 Pump Relay Installation Wiring Diagram...