Once the failure is fixed, the control unit needs to be reset to its 

normal operating status. Press the “Reset/Test button on the 

front of the control unit to reset it.

Caution.

  It is advisable to repeat the operating test at least 

once a year, or after a prolonged period of stoppage and in any 

case, every time the detector is replaced. 

Caution.

 The average lifetime of the UR13 and UR20S detec-

tors is 5 years from installation date. They must be replaced 

before the end of the 5th year of use. The average lifetime of 

detectors is calculated for use in a typical environment, nor-

mally free from polluting agents (gases, solvents etc.). 

More frequent and higher concentrations of these substances 

can accelerate the normal oxidisation process of the sensing 

element, subsequently shotening its lifetime.

Gas Alarm

If an alarm signals a gas leak or the presence of carbon  

monoxide, proceed as follows:

- put out flames and switch off all gas equipment;

- do not for any reason switch on or off lights or any electrical  

   equipment;

- open doors and windows to air the environment;

- look for and eliminate the cause of the alarm. If this is not  

   possible, leave the building and contact emergency services  
  from outside.

Environmental compatibility and 

disposal

This product has been designed and constructed using 

 

materials and processes that take into account the 

environmental issue. Refer to the following notes for 

disposal of the product at the end of its working life, 

or when it is replaced:

- for disposal purposes, this product is classified 

as an  

  electric and electronic device: do not dispose of it with  

  normal household waste, in particular as regards the  

  printed  

  circuit;

- comply with all local laws in force;

- as far as possible reuse basic materials to keep  
  environmental  impact to a minimum;
- use local depots and waste recycling companies, or contact  
  the supplier or manufacturer to return used products or to  
   ask for information on environmental compatibility and waste  
  disposal; 
- the product packaging can be reused. Keep it for future use  
  or to return the product to the supplier.

Problem

Possible cause

NC valve does not open

-  Valve not connected
-  Alarm in progress
-  Detector warm-up phase in    
   progress
- All detector defective
- General failure event occurring

NO valve does not close

-  Valve not connected
-  Connection cables cut
-  No alarm active

“Reset/Test” button 
does not reset to initial 
conditions

-  Alarm in progress
-  Failure occurring in control unit

Troubleshooting

+

    

Power supply 12 Vac/dc (positive)

+

   

OC output 12 Vac/dc (positive)

C

   Alarm 

Alarm relay output (common)

NC

 Alarm 

Alarm relay output (Normally Closed contact)

NO

 Alarm 

Alarm relay output (Normally Open contact)

C

   Abnormality  Alarm relay output (common)

NC

 Abnormality  Alarm relay output (Normally Closed contact)

NO

 Abnormality  Alarm relay output (Normally Open contact)

UR13 detector connections

C1,C2,C3,C4

 Detector input (

C, 

common)

S1,S2,S3,S4 

Detector input (

S,

 signal)

A1,A2,A3,A4

 Detector input (

A,

 power supply 6.5V)

UR20S detector connections

C1,C2,C3,C4 

Detector input (

-12...24V,

 negative power supply/signal)

S1,S2,S3,S4  

Detector input (

+4...20mA,

 positive signal)

A1,A2,A3,A4

 Detector input (

+12...24V,

 positive power supply/signal)

1.   TB1 - Power supply terminals 12 Vac/dc

2.   Protection fuse 1A

3.   TB2 - “Alarm” relay terminals

4.   TB3 - “Abnormlity” relay terminals

5.   CN1 connector and service Jumper J1

6.   Set up jumper:

       E1 – operating mode

       E2 – Alarm relay operating mode

       E3 – omitted=UR13 on input 1 and 2, A=UR20S on inputs 1  

               B=UR20S on inputs and 2  

       E4 – omitted=UR13 on input 1 and 2, A=UR20S on inputs 1  

               B=UR20S on inputs and 2  

7.   Connector P1 (communication – not used)  

8.   LED signalling presence of voltage  

9.   LED signalling general failure 

10. Reset/Test button  

11. TB7 - B4 gas detector connection terminals  

12. Jumper E11÷E12 for configuration of inputs B4 detector:

      E11 - Sel. power supply: A=6.5V (UR13), B=12V (UR20S)  

      E12 - Sel. input A=threshold (UR13), B=4...20mA (UR20S) 

      Jumper E9÷E10 for configuration of inputs B3 detector:  

      E9 - Sel. power supply: A=6.5V (UR13), B=12V (UR20S)  

      E10 - Sel. input A=threshold (UR13), B=4...20mA (UR20S)

13 TB6 - B3 gas detector connection terminals  

14 TB5 - B2 gas detector connection terminals  

15 Jumper E7÷E8 for configuration of inputs B2 detector:

      E7 - Sel. power supply: A=6.5V (UR13), B=12V (UR20S) 

      E8 - Sel. input A=threshold (UR13), B=4...20mA (UR20S)  

      Jumper E5÷E6 for configuration of inputs B1 detector:  

      E5 - Sel. power supply: A=6.5V (UR13), B=12V (UR20S)  

      E6 - Sel. input A=threshold (UR13), B=4...20mA (UR20S)

16 TB4 - B1 gas detector connection terminals 

17 Gas alarm LED  

18 Detector failure LED

Terminal board

Содержание CIVIC4

Страница 1: ...WattsWater eu CIVIC4 Gas detection control Installation manual Installation and Operation Manual Manuale di Installazione e Uso UK IT ...

Страница 2: ...g Operation Gas Alarm Environmental compatibility and disposal Troubleshooting Terminal Board Connection diagrams Dimensions Indice Generale Caratteristiche tecniche Installazione Messa in servizio Funzionamento Allarme gas Compatibilità ambientale e smaltimento Analisi dei guasti Morsettiera Schemi di collegamento Ingombri ...

Страница 3: ...Vac Output connections 3 terminals of 2 5 mm2 for C NC NO relay Visual alarms 1 green LED power on 1 yellow LED general abnormality 4 yellow LEDs failure for each detector line 4 red LEDs gas alarm for each detector line Audible alarms 1 buzzer noise level 60db at 1m Reset Test button 1 for alarm Reset and detector Test Enclosure RAL7035 grey self extinguishing plastic house Dimensions and weight ...

Страница 4: ...insulation sized for uninterrupt ed use for the power utilised See Technical features For connecting the relay output use wires with a minimum diameter of 1 5 mm2 Prepare wiring connections according to the electrical diagrams contained in these instructions UR13 or UR20S detector Prepare wiring connections according to the electrical dia grams contained in these instructions using wires with a mi...

Страница 5: ...rm buzzer Intermittent sound Intermittent sound Failure relay De energised Energised General failure LED Yellow On Off Caution The repeated use or high concentration of interfering substances alcohol lighter fluid etc can cause permanen damage to the sensor and put the device out of order Detector failure test Simulate a failure in the detector as follows disconnect the cable of the detector and v...

Страница 6: ...open Valve not connected Alarm in progress Detector warm up phase in progress All detector defective General failure event occurring NO valve does not close Valve not connected Connection cables cut No alarm active Reset Test button does not reset to initial conditions Alarm in progress Failure occurring in control unit Troubleshooting Power supply 12 Vac dc positive OC output 12 Vac dc positive C...

Страница 7: ...conditioned on the buyer s assent to Watts terms and conditions found on its website at www wattsindustries com Watts hereby objects to any term different from or additional to Watts terms contained in any buyer communication in any form unless agreed to in a writing signed by an officer of Watts Guarantee Watts products are thoroughly tested The said guarantee covers solely replacement or at the ...

Страница 8: ...é con 1 contatto SPDT 8A 250Vac Collegamenti uscite n 3 morsetti of 2 5 mm2 per relé C NC NO Segnalazioni luminose 1 LED verde alimentazione presente 1 LED giallo anomalia generale 4 LED gialli anomalia per ogni linea sonde 4 LED rossi allarme gas per ogni linea sonde Segnalazioni acustiche 1 cicalino di intensità sonora 60db a 1m Pulsante Reset Test 1 per Reset allarmi e Test sonde Contenitore Ma...

Страница 9: ... a 12 Vac dc utilizzare trasformatori a doppio isolamento dimensionati per un utilizzo continuativo per la potenza impegnata Vedi Dati Tecnici Per il collegamento dell uscita a relè utilizzare cavi con sezione minima di 1 5 mm2 Predisporre i collegamenti secondo gli schemi elettrici conte nuti nelle presenti istruzioni Sonde UR13 o UR20S Predisporre i collegamenti secondo gli schemi elettrici cont...

Страница 10: ...set Test per riportare la centrale al funzionamento normale verificando il ripris tino delle condizioni delle varie interfacce Normale funzionamento È la fase di normale operatività della centrale durante la quale sono attivi sia il monitoraggio per l allarme gas sia l autodiag nosi per le anomalie di impianto sonda e di sistema centrale In questa fase ed in assenza di allarme e anomalia la centra...

Страница 11: ...ligatori amente essere sostituite prima dello scadere del 5 anno di utilizzo La vita media delle sonde è calcolata tenendo conto di un utilizzo tipico in ambiente normalmente libero da agenti inquinanti gas soventi etc Una presenza più frequente ed in concentrazioni più elevate di tali sostanze può accelerare il normale processo di ossidazione dell elemento sensibile con conseguente diminuzione de...

Страница 12: ...estione del recupero e dello smaltimento delle apparecchiature Watts Industries Italia srl aderisce al consorzio EcoPED Consorzio Nazionale Riciclo Piccoli Elettrodomestici Lo smaltimento abu sivo del prodotto da parte dell utente comporta l applicazione di sanzioni amministrative previste dalla normativa vigente Le descrizioni e le fotografie contenute nel presente documento si intendono fornite ...

Отзывы: