Installation

Mounting

Ensure correct environmental conditions (See Technical features).

CIVIC4 control unit

To guarantee the correct protection rating for the device it 

must be installed in an electric panel manufactured according 

to the laws in force for workplaces and that can also house 

the power supply system. Mount the control unit on a rail (to 

DIN EN 50022), using accessories for standard electric panels. 

It can be installed on a mounting plate or in DIN rail modules.

UR13 (UR20S) detectors

To be used for wall-mounting (vertical), attached by plastic 

screws and anchors. To install, insert a screwdriver in the 

recess at the bottom of the enclosure to open it; avoid damage 

to the sensor and do not touch the calibration devices.    
The detectors must be correctly positioned for the system to- 

in zones with constant natural air circulation
- in zones free of dust and dirt that could clog up the sensor  

  and make it ineffective
- never near running water, exhaust vents, windows, openings etc.
- at a suitable distance from the gas-fuelled equipment to  

  avoid the system taking inappropriate action due to possible  

  functional loss.
The positioning also depends on the type of gas that is to be 

detected, in particular:
- UR13: Methane gas - high, about 20-30 cm from ceiling
- UR13: LPG - low, about 20-30 cm from floor
- UR13: CO - about 1.5 m from floor
For new plants, the detector must be installed at the last  

possible moment so that typical worksite activities (particularly 

welding, painting, sealing etc.), do not damage the actual 

detector (particularly the sensing part).

UR20S detectors

See installation instructions on dedicated data sheet.

Electrical connections

Normal electric cables can be used. Still, if detectors are to 

be installed in environments with high exposure to EMI, it is  

advisable to use shielded cables. The detection system must 

always be operating, so power switches or other devices that 

could inadvertently make the detector inoperative must not be 

used. Do not touch the sensing element and the electronic 

circuits for any reason whatsoever. Tampering of any kind may 

cause the system to operate incorrectly.
Ensure compliance with all current electric standards.

CIVIC4 control unit

The control unit must be powered at 12 Vac/dc; use 

transformers with double insulation, sized for uninterrupt-

ed use for the power utilised (See Technical features). 

 

For connecting the relay output use wires with a minimum 

diameter of 1.5 mm

2

. Prepare wiring connections according to 

the electrical diagrams contained in these instructions. 

UR13 or UR20S detector 

Prepare wiring connections according to the electrical dia-

grams contained in these instructions, using wires with a min-

imum diameter of 1.5 mm

2

 for a maximum length of 50 m. for 

each detector.

Commisioning

The CIVIC4 control unit and the UR13 or UR20S detectors are 

safety control devices, therefore they must not be tampered 

with; do not touch the sensor or the electronics for any reason 

whatsoever. Carry out the following controls:
- the power supply for the control unit must comply with the  

   values provided (12 Vac/dc ± 10%)
- make sure the power consumed by any devices connected    

  to the relay terminals is below or the same as the maximum  

  capacity of the contacts (See Technical features)
- if there are no detectors on the respective control unit 

 

  terminals, resistances 18 KOhm ¼W 5% are supplied as  

  standard (terminals C and S). In any case, these terminals  

  must be disconnected from the inputs where there are 

   detectors
- the detectors must be compatible with the type of gas  

  to monitor and correctly connected to the control unit.
Depending on the type of detector to connect, jumper pairs 

E5-E6, E7-E8, E9-E10, E11-E12 must be positioned for each 

detector as follows (example for detector 1):

- the operating mode (positive or negative logic) selected must be  

  consistent with the system choices. As regards this, check the  

  position of Jumper E1 (See Operation).
- the operating mode selected for the relay must be consistent  

  with the system choices. As regards this, check the position of  

 Jumper E2 (See Operation).
- test the gas alarm and the detector failure condition events  

  (See Operation).

Operation

The Jumper E1 can be used to select the operating mode 

(positive or negative logic). The control unit signals its operat-

ing status through LEDs. Depending on the operating mode 

selected through Jumper E1, in a normal situation (no alarm), 

the LEDs and the relays are as follows:
positive operating logic:  LEDs on; relays energised 

negative operating logic: LEDs off; relays de-energised 
If the negative operating logic is selected, the alarm relay can 

be permanently or impulse controlled, depending on the  

position of Jumper E2: 

Warning 

 

To enable the UR20S 
sensors to operate, it 
is also necessary to 
set jumpers E3 and 
E4 as instructed in the 
chapter: 

Description of 
device.

Содержание CIVIC4

Страница 1: ...WattsWater eu CIVIC4 Gas detection control Installation manual Installation and Operation Manual Manuale di Installazione e Uso UK IT ...

Страница 2: ...g Operation Gas Alarm Environmental compatibility and disposal Troubleshooting Terminal Board Connection diagrams Dimensions Indice Generale Caratteristiche tecniche Installazione Messa in servizio Funzionamento Allarme gas Compatibilità ambientale e smaltimento Analisi dei guasti Morsettiera Schemi di collegamento Ingombri ...

Страница 3: ...Vac Output connections 3 terminals of 2 5 mm2 for C NC NO relay Visual alarms 1 green LED power on 1 yellow LED general abnormality 4 yellow LEDs failure for each detector line 4 red LEDs gas alarm for each detector line Audible alarms 1 buzzer noise level 60db at 1m Reset Test button 1 for alarm Reset and detector Test Enclosure RAL7035 grey self extinguishing plastic house Dimensions and weight ...

Страница 4: ...insulation sized for uninterrupt ed use for the power utilised See Technical features For connecting the relay output use wires with a minimum diameter of 1 5 mm2 Prepare wiring connections according to the electrical diagrams contained in these instructions UR13 or UR20S detector Prepare wiring connections according to the electrical dia grams contained in these instructions using wires with a mi...

Страница 5: ...rm buzzer Intermittent sound Intermittent sound Failure relay De energised Energised General failure LED Yellow On Off Caution The repeated use or high concentration of interfering substances alcohol lighter fluid etc can cause permanen damage to the sensor and put the device out of order Detector failure test Simulate a failure in the detector as follows disconnect the cable of the detector and v...

Страница 6: ...open Valve not connected Alarm in progress Detector warm up phase in progress All detector defective General failure event occurring NO valve does not close Valve not connected Connection cables cut No alarm active Reset Test button does not reset to initial conditions Alarm in progress Failure occurring in control unit Troubleshooting Power supply 12 Vac dc positive OC output 12 Vac dc positive C...

Страница 7: ...conditioned on the buyer s assent to Watts terms and conditions found on its website at www wattsindustries com Watts hereby objects to any term different from or additional to Watts terms contained in any buyer communication in any form unless agreed to in a writing signed by an officer of Watts Guarantee Watts products are thoroughly tested The said guarantee covers solely replacement or at the ...

Страница 8: ...é con 1 contatto SPDT 8A 250Vac Collegamenti uscite n 3 morsetti of 2 5 mm2 per relé C NC NO Segnalazioni luminose 1 LED verde alimentazione presente 1 LED giallo anomalia generale 4 LED gialli anomalia per ogni linea sonde 4 LED rossi allarme gas per ogni linea sonde Segnalazioni acustiche 1 cicalino di intensità sonora 60db a 1m Pulsante Reset Test 1 per Reset allarmi e Test sonde Contenitore Ma...

Страница 9: ... a 12 Vac dc utilizzare trasformatori a doppio isolamento dimensionati per un utilizzo continuativo per la potenza impegnata Vedi Dati Tecnici Per il collegamento dell uscita a relè utilizzare cavi con sezione minima di 1 5 mm2 Predisporre i collegamenti secondo gli schemi elettrici conte nuti nelle presenti istruzioni Sonde UR13 o UR20S Predisporre i collegamenti secondo gli schemi elettrici cont...

Страница 10: ...set Test per riportare la centrale al funzionamento normale verificando il ripris tino delle condizioni delle varie interfacce Normale funzionamento È la fase di normale operatività della centrale durante la quale sono attivi sia il monitoraggio per l allarme gas sia l autodiag nosi per le anomalie di impianto sonda e di sistema centrale In questa fase ed in assenza di allarme e anomalia la centra...

Страница 11: ...ligatori amente essere sostituite prima dello scadere del 5 anno di utilizzo La vita media delle sonde è calcolata tenendo conto di un utilizzo tipico in ambiente normalmente libero da agenti inquinanti gas soventi etc Una presenza più frequente ed in concentrazioni più elevate di tali sostanze può accelerare il normale processo di ossidazione dell elemento sensibile con conseguente diminuzione de...

Страница 12: ...estione del recupero e dello smaltimento delle apparecchiature Watts Industries Italia srl aderisce al consorzio EcoPED Consorzio Nazionale Riciclo Piccoli Elettrodomestici Lo smaltimento abu sivo del prodotto da parte dell utente comporta l applicazione di sanzioni amministrative previste dalla normativa vigente Le descrizioni e le fotografie contenute nel presente documento si intendono fornite ...

Отзывы: