Watts Water Technologies, Inc.
EN
General
The CIVIC4 control unit can be used to connect one detector (model UR13 or UR20S) to create gas detection systems in envi-
ronments such as boiler rooms, workshops, warehouses, laboratories etc.; the incorporated alarm relay can be used to control a
solenoid valve or an accessory device (siren, flashing light, extractor, etc.). The installation of a gas or carbon monoxide detection
system does not constitute a release from compliance with all regulations for the installation and use of gas devices and with the
relative safety standards and legal provisions in force for this kind of system. Installation, periodic inspections and maintenance of
devices and systems must be carried out by qualified service technicians.
Technical features
CIVIC4 control unit (data with UR20S detectors in brackets)
Power supply:
12Vac/dc ± 10%
Consumption with 1 detector:
About 160mA (320mA)
Consumption with 4 detectors:
About 280mA (920mA)
Connections:
Two terminals of 2.5 mm
2
Protection:
Power input fuse 1A 5x20mm
Inputs:
4 for UR13 detector or UR20S detectors (different types of gas)
Detector terminations:
Three terminals of 2.5 mm
2
: C (-12...24V); S (+4…20mA); A (+12...24V)
Max cable run length:
50 m for each detector
Diameter of the 3 wires:
1.5 mm
2
Alarm output:
1 relay with one contact SPDT 8A 250Vac
Failure output:
1 relay with one contact SPDT 8A 250Vac
Output connections:
3 terminals of 2.5 mm
2
for C-NC-NO relay
Visual alarms:
1 green LED: power on
1 yellow LED: general abnormality
4 yellow LEDs: failure for each detector line
4 red LEDs: gas alarm for each detector line"
Audible alarms:
1 buzzer noise level > 60db at 1m
“Reset/Test” button:
1 for alarm Reset and detector Test
Enclosure:
RAL7035 grey, self-extinguishing plastic house
Dimensions and weight:
158x90x58 mm (9 modules to standard DIN 43880), 250 g
Mounting:
Back panel Omega DIN rail (EN 50022)
Protection rating:
IP20; IP40 when correctly installed in electric panel
Room temperature:
0÷50 °C
Humidity
≤90% RH (non condensing)
EC Conformity
Product standards:
Standards EN 60079-29-1; CEI 216-5/1
LV Directives/Standards
LV 2014/35/EU, Standard EN 60730-1
EMC Directives/Standards
EMC 2014/30/EU, Standard EN 50270
UR13 (UR20S) detectors
Power supply
from the CIVIC4 control unit
Consumption
40mA (200mA)
Connections
three terminals of 2.5 mm
2
per detector: C (-12...24V); S (+4…20mA); A
(+12...24V)
Models
Methane Gas Cod. 0940561
LPG Cod. 0940562
Carbon monoxide Cod. 0940563
UR20S Models
Various gases, see dedicated data sheet
Calibration:
UR13: 10% LEL of Methane
UR13: 12% LEL of Isobutane
UR13: 200ppm of CO
(UR20S: 20% LEL combustibles, 100ppm CO)
Enclosure:
Self-extinguishing plastic house
Dimensions and weight:
66x90x45 mm (depending on model), 65 g
Mounting:
Wall-mounted using plastic screws and anchors
Protection:
IP44 (IP44, IP55 or IP65 depending on model)
Room temperature:
0÷50°C (-20÷50°C)
Humidity:
≤90% RH (non condensing)
LV Directives/Standards
Not applicable
EMC Directives/Standards
EMC 2014/30/EU, Standard EN 50270