General

The CIVIC4 control unit can be used to connect one detector (model UR13 or UR20S) to create gas detection systems in envi-

ronments such as boiler rooms, workshops, warehouses, laboratories etc.; the incorporated alarm relay can be used to control a 

solenoid valve or an accessory device (siren, flashing light, extractor, etc.). The installation of a gas or carbon monoxide detection 

system does not constitute a release from compliance with all regulations for the installation and use of gas devices and with the 

relative safety standards and legal provisions in force for this kind of system. Installation, periodic inspections and maintenance of 

devices and systems must be carried out by qualified service technicians.

Technical features

CIVIC4 control unit (data with UR20S detectors in brackets)

Power supply:

12Vac/dc ± 10%

Consumption with 1 detector:

About 160mA (320mA) 

Consumption with 4 detectors:

About 280mA (920mA) 

Connections:

Two terminals of 2.5 mm

2

Protection:

Power input fuse 1A 5x20mm

Inputs:

4 for UR13 detector or UR20S detectors (different types of gas)

Detector terminations:

Three terminals of 2.5 mm

2

: C (-12...24V); S (+4…20mA); A (+12...24V)

Max cable run length:

50 m for each detector 

Diameter of the 3 wires:

1.5 mm

2

Alarm output:

1 relay with one contact SPDT 8A 250Vac

Failure output:

1 relay with one contact SPDT 8A 250Vac

Output connections:

3 terminals of 2.5 mm

2

 for C-NC-NO relay

Visual alarms:

1 green LED: power on  
1 yellow LED: general abnormality  
4 yellow LEDs: failure for each detector line  
4 red LEDs: gas alarm for each detector line"

Audible alarms: 

1 buzzer noise level > 60db at 1m

“Reset/Test” button:

1 for alarm Reset and detector Test

Enclosure:

RAL7035 grey, self-extinguishing plastic house

Dimensions and weight:

158x90x58 mm (9 modules to standard DIN 43880), 250 g

Mounting:

Back panel Omega DIN rail (EN 50022)

Protection rating:

IP20; IP40 when correctly installed in electric panel

Room temperature:

0÷50 °C

Humidity

≤90% RH (non condensing)

EC Conformity
Product standards:

Standards EN 60079-29-1; CEI 216-5/1

LV Directives/Standards

LV 2014/35/EU, Standard EN 60730-1

EMC Directives/Standards

EMC 2014/30/EU, Standard EN 50270

  UR13 (UR20S) detectors

Power supply

from the CIVIC4 control unit

Consumption

40mA (200mA)

Connections

three terminals of 2.5 mm

2

 per detector: C (-12...24V); S (+4…20mA); A 

(+12...24V)

Models

Methane Gas Cod. 0940561
LPG Cod. 0940562
Carbon monoxide Cod. 0940563

UR20S Models

Various gases, see dedicated data sheet

Calibration:

UR13: 10% LEL of Methane
UR13: 12% LEL of Isobutane
UR13: 200ppm of CO
(UR20S: 20% LEL combustibles, 100ppm CO)

Enclosure:

Self-extinguishing plastic house

Dimensions and weight:

66x90x45 mm (depending on model), 65 g

Mounting:

Wall-mounted using plastic screws and anchors

Protection:

IP44 (IP44, IP55 or IP65 depending on model)

Room temperature:

0÷50°C (-20÷50°C)

Humidity:

≤90% RH (non condensing)

LV Directives/Standards

Not applicable

EMC Directives/Standards

EMC 2014/30/EU, Standard EN 50270

Содержание CIVIC4

Страница 1: ...WattsWater eu CIVIC4 Gas detection control Installation manual Installation and Operation Manual Manuale di Installazione e Uso UK IT ...

Страница 2: ...g Operation Gas Alarm Environmental compatibility and disposal Troubleshooting Terminal Board Connection diagrams Dimensions Indice Generale Caratteristiche tecniche Installazione Messa in servizio Funzionamento Allarme gas Compatibilità ambientale e smaltimento Analisi dei guasti Morsettiera Schemi di collegamento Ingombri ...

Страница 3: ...Vac Output connections 3 terminals of 2 5 mm2 for C NC NO relay Visual alarms 1 green LED power on 1 yellow LED general abnormality 4 yellow LEDs failure for each detector line 4 red LEDs gas alarm for each detector line Audible alarms 1 buzzer noise level 60db at 1m Reset Test button 1 for alarm Reset and detector Test Enclosure RAL7035 grey self extinguishing plastic house Dimensions and weight ...

Страница 4: ...insulation sized for uninterrupt ed use for the power utilised See Technical features For connecting the relay output use wires with a minimum diameter of 1 5 mm2 Prepare wiring connections according to the electrical diagrams contained in these instructions UR13 or UR20S detector Prepare wiring connections according to the electrical dia grams contained in these instructions using wires with a mi...

Страница 5: ...rm buzzer Intermittent sound Intermittent sound Failure relay De energised Energised General failure LED Yellow On Off Caution The repeated use or high concentration of interfering substances alcohol lighter fluid etc can cause permanen damage to the sensor and put the device out of order Detector failure test Simulate a failure in the detector as follows disconnect the cable of the detector and v...

Страница 6: ...open Valve not connected Alarm in progress Detector warm up phase in progress All detector defective General failure event occurring NO valve does not close Valve not connected Connection cables cut No alarm active Reset Test button does not reset to initial conditions Alarm in progress Failure occurring in control unit Troubleshooting Power supply 12 Vac dc positive OC output 12 Vac dc positive C...

Страница 7: ...conditioned on the buyer s assent to Watts terms and conditions found on its website at www wattsindustries com Watts hereby objects to any term different from or additional to Watts terms contained in any buyer communication in any form unless agreed to in a writing signed by an officer of Watts Guarantee Watts products are thoroughly tested The said guarantee covers solely replacement or at the ...

Страница 8: ...é con 1 contatto SPDT 8A 250Vac Collegamenti uscite n 3 morsetti of 2 5 mm2 per relé C NC NO Segnalazioni luminose 1 LED verde alimentazione presente 1 LED giallo anomalia generale 4 LED gialli anomalia per ogni linea sonde 4 LED rossi allarme gas per ogni linea sonde Segnalazioni acustiche 1 cicalino di intensità sonora 60db a 1m Pulsante Reset Test 1 per Reset allarmi e Test sonde Contenitore Ma...

Страница 9: ... a 12 Vac dc utilizzare trasformatori a doppio isolamento dimensionati per un utilizzo continuativo per la potenza impegnata Vedi Dati Tecnici Per il collegamento dell uscita a relè utilizzare cavi con sezione minima di 1 5 mm2 Predisporre i collegamenti secondo gli schemi elettrici conte nuti nelle presenti istruzioni Sonde UR13 o UR20S Predisporre i collegamenti secondo gli schemi elettrici cont...

Страница 10: ...set Test per riportare la centrale al funzionamento normale verificando il ripris tino delle condizioni delle varie interfacce Normale funzionamento È la fase di normale operatività della centrale durante la quale sono attivi sia il monitoraggio per l allarme gas sia l autodiag nosi per le anomalie di impianto sonda e di sistema centrale In questa fase ed in assenza di allarme e anomalia la centra...

Страница 11: ...ligatori amente essere sostituite prima dello scadere del 5 anno di utilizzo La vita media delle sonde è calcolata tenendo conto di un utilizzo tipico in ambiente normalmente libero da agenti inquinanti gas soventi etc Una presenza più frequente ed in concentrazioni più elevate di tali sostanze può accelerare il normale processo di ossidazione dell elemento sensibile con conseguente diminuzione de...

Страница 12: ...estione del recupero e dello smaltimento delle apparecchiature Watts Industries Italia srl aderisce al consorzio EcoPED Consorzio Nazionale Riciclo Piccoli Elettrodomestici Lo smaltimento abu sivo del prodotto da parte dell utente comporta l applicazione di sanzioni amministrative previste dalla normativa vigente Le descrizioni e le fotografie contenute nel presente documento si intendono fornite ...

Отзывы: