A.3 Modbus Communication Information
NOTE:
The Temperature Controller supports the MODBUS RTU mode of transmission. The default
settings are: 19200 Baud Rate, one start bit, eight data bits, one stop bit, & no parity bit.
TEMPERATURE CONTROLLER MODBUS POINTS
MODBUS
Data
Address
Menu
Item
Menu Item
Description
Units &
Range
Default/Comments
Register
Type
Ref.
Location
1
Top
Value
Outlet
Temperature
40-205°F
Same value as front
display
Read
Only
1
2
Setpoint
Setpoint
40-180°F
140°F, Address to
change value
Holding
1
4
w Out
Working
Output
0-100%
Valve Position
Read
Only
2
364
Mod 1A
PV
Module 1 C PV
0-150 GPM
Domestic Hot Water
Flow
Read
Only
2
370
Mod 3A
PV
Module 3 C PV
40-190°F
Boiler Water Inlet
Temperature
Read
Only
2
373
Mod 4A
PV
Module 4 C PV
40-180°F
Domestic Hot Water
Inlet Temperature
Read
Only
2
379
Mod 6A
PV
Module 6 C PV
0-100 PSI
DHW Pressure Drop
Across Hx
Read
Only
2
10249
AnAlm 1
Alarm 1 Out
Status:
0: Good
1: Failed
Read Alarm Output
Read
Only
2
10265
AnAlm 2
Alarm 2 Out
Status:
0: Good
1: Failed
Read Alarm Output
Read
Only
2
10273
AnAlm 3
Alarm 3 Out
Status:
0: Good
1: Failed
Read Alarm Output
Read
Only
2
10297
AnAlm 4
Alarm 4 Out
Status:
0: Good
1: Failed
Read Alarm Output
Read
Only
2
10313
AnAlm 5
Alarm 5 Out
Status:
0: Good
1: Failed
Read Alarm Output
Read
Only
2
10329
AnAlm 6
Alarm 6 Out
Status:
0: Good
1: Failed
Read Alarm Output
Read
Only
2
10345
AnAlm 7
Alarm 7 Out
Status:
0: Good
1: Failed
Read Alarm Output
Read
Only
2
10361
AnAlm 8
Alarm 8 Out
Status:
0: Good
1: Failed
Read Alarm Output
Read
Only
2
REFERENCE DOCUMENT
: Eurotherm 3504/3508 Engineering Manual (HA027988 Iss 19)