WattMaster WHP
Section
3
Programming
3-31
Setpoint Screen #12
Setpoint Screens #13
Note:
Due to memory limitations in the Loop Controller, the maximum amount of
calibration offset is 10.0
°
F.
Setpoint Screen #14
Setpoint Screen #15
If you configured the system for Variable Speed Pumping with a
Pressure Sensor for proof of flow, the Loop Controller can send
a signal to all the Heat Pumps to open their Isolation Valves
whenever a Hi Limit Pressure is exceeded. If the Heat Pumps do
not control an Isolation Valve, then the only reaction is to
reduce the variable speed pump voltage signal.
WHP Loop Setpoints
Isolation Valves Set
Open if PSI is Above
Hi Limit...: xxx PSI
Minimum
Default
Maximum
Hi Limit
1 PSI
50 PSI
50 PSI
The Thermister Type III Sensor readings can be calibrated.
Enter a Positive value to increase the reading or a Negative
value to decrease the reading. If no sensor is attached, the
calibration offset will still allow a value to be input and read for
diagnostic purposes.
SENSOR CALIBRATION
RWT xxx.x
°
xxxx.x
°
°
SWT xxx.x
°
°
xxxx.x
°
°
OAT xxx.x
°
°
xxxx.x
°
°
Minimum Default Maximum
Return Water RWT
-10.0°F
0.0°F
+10.0°F
Supply Water SWT
-10.0°F
0.0°F
+10.0°F
Outdoor Air OAT
-10.0°F
0.0°F
+10.0°F
Alarms can be configured to light the LED on the front of the
System Manager by setting Alarms to Enabled, if you do not
wish to report alarms, select Disabled.
WHP Loop Setpoints
Alarms: Enabled
Use Left/Right Arrow
Use this screen to configure the relays on the expansion board
for heat ADDITION, REJECTION or NOT USED. All 8
relays come up one at a time.
WHP Loop Setpoints
Relay Configurations
Rly 1: ADDITION
Use Left/Right Arrow
Содержание Water Source Heat Pump
Страница 1: ...WHP Water Source Heat Pump Design Installation Operations Manual Revision 02A...
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 22: ...Section 1 WattMaster WHP 1 16 Design Guide Notes...
Страница 48: ......
Страница 80: ...Section 3 WattMaster WHP 3 32 Programming Notes...
Страница 125: ...WattMaster WHP Section 4 Start Up and Troubleshooting 4 43 Notes...