Features

 

• 

Control Panel for extinguishing systems with two zones 

• 

Surface mounted or flush mounted in a wall 

• 

Delivered as a steel cabinet with lockable front panel 

• 

Can be used together with conventional and analogue ad-
dressable fire alarm systems 

• 

Designed to meet EMC requirements and CE standards 

• 

Monitored inputs and outputs 

• 

Indicating panel with operating buttons and LED indicators 

• 

Designed for duplicated 24V DC operating voltage 

• 

All inputs / outputs are connected to integrated Extinguishing 
Release Module BA-40 

• 

Plug terminals for easy connection

 

Application / Description

 

BA-45 is a control panel used together with automatic fire extin-
guishing systems. 

The panel consists of 2 zone units. Each zone unit controls and 
monitors an extinguishing zone, which can be an area, a room, a 
machine, an electrical cabinet etc. Each zone unit has 5 inputs, 4 
outputs and 8 LED indicators, plus 2 inhibit buttons. The BA-45's 
common functions consist of 4 inputs, 3 LED indicators and 3 
operating buttons.  

Several BA-45's can be used if more than two extinguishing 
zones are required. 

By means of a DIP-switch (S1), a delay period can be set. It is 
also possible to revert the common fault output (39), plus turn off 
the short circuit monitoring for all inputs.

 

Zone unit

 

Inputs

 

• 

Signal input 1 and 2, break and short circuit monitored. 

• 

Activation of signal output 1 or 2 triggers the delay period for 
release. Activation of signal output 2 before the delay period 
ends activates the release output when the delay period ends.  

• 

Manual release. 2-stage manual release function. Stage 1 
activates alarm for the zone, stage 2 gives release. Break and 
short circuit monitored. Two-wire connection. 

• 

Automatic release inhibited via inhibit button on front panel or 
via input for external button. The input is break and short circuit 
monitored. Can also be used as "Hold" function during the 
delay period. 

• 

Inhibit button for control output for 1st alarm.  

• 

Monitoring of pressure in extinguisher tank. Closed contacts at 
normal pressure. Break and short circuit monitored.

  

 

Outputs

 

• 

Release circuit with delayed action. 22-24V DV, secured 1A.  
3A current limitation in case of brief current surge (initiators). 
Break and short circuit monitored. 

• 

Control output at activation of one of the signal inputs. Transis-
tor output, 100mA. (Inhibited via front panel button). 

• 

Extinguisher released. Potential free relay output. 

• 

Automatic release inhibited. Transistor output, 100mA.

 

 

 

 

 

 

 

 

 

 

 

LED indicators 

 

Status indicators:

 

• 

Red indicator activates at alarm on one of the signal inputs, the 
delay period starts (1st alarm). 

• 

Red indicator activates at release of extinguisher. 

• 

Yellow indicator activates when automatic release is inhibited. 

• 

Yellow indicator activates when control output for 1st alarm is 
inhibited.

 

 

Fault indicators:

 

• 

Yellow indicator shows failure on release circuit. 

• 

Yellow indicator activates if release pressure in extinguisher 
tank is too low. 

• 

Yellow indicator activates if there is a failure on control input 1 
or 2. 

• 

Yellow indicator shows failure on manual release circuit, circuit 
for inhibit of automatic release or pressure monitoring circuit.

 

 

Operating buttons:

 

• 

Inhibit button for automatic release. 

• 

Inhibit button for control output on 1st alarm. 

 

Common Functions

 

Inputs

 

• 

24V DC power supply, circuit 1 and circuit 2, secured. 

• 

Silence of sounders. New alarm in other zone will reactivate 
sounders. 

• 

Reset of unit.

 

 

Outputs

 

• 

Sounder alarm output at the first incoming control signal. 
Voltage output across relay, 24V DC / 0,5A, monitored and 
secured. Cancelled at activation of input "Silence Sounder 
Alarm". Reactivated at new alarm in new zone. 

• 

Control output at first incoming control signal. Potential free 
relay. 

• 

Common fault output. Transistor output, 100 mA. Can be 
reverted by means of DIP-switch S1.3. 

• 

24V DC output for common power supply to control outputs. 
Monitored and secured with 0,5A. 

 

Control Panel for Extinguishing Systems                       BA-45

 