WattMaster WHP
Section 4
Start-Up and Troubleshooting
4-21
5.0 Troubleshooting
5.1
General Troubleshooting
The following is a guide to assist in troubleshooting the WattMaster WHP System. It is
provided as a systematic approach to determining and resolving common system
problems.
5.1.1
Communications Troubleshooting Checklist
No WHP or Loop Controller Units are Communicating
•
Is the CommLink II connected and plugged in?
•
Is the CommLink II installed, a single or multiple loop version. A jumper in the
CommLink can be set for “Single” or “Multi”. On the WHP system is considered a
Multiple Loop version and the CommLink jumper must be set on Multi.
•
Are Comm Loop voltages correct? See the Comm Loop troubleshooting guides.(page
4-24)
•
Is the Comm Loop open or shorted?
•
Is the CommLink II connected and plugged in?
•
Is the MiniLink Voltage correct?
•
Are the WHP and Loop Controller address switches set correctly? See the addressing
chart. (WHP Loop Controller should always be set to address 30, see Figure 4-10)
•
Is the MiniLink address switch set correctly? See the addressing chart.(see Figure 4-
10)
•
Are the WHP and Loop Controllers powered? Check 24 VAC to the controllers.
•
Is the System Manager connected to the Local Communications loop?
Some WHP Units are communicating but others are not:
•
Are the WHP Controller address switches set correctly? See the addressing chart.
•
Is the WHP Loop Controller address switch set correctly? See the addressing chart.
•
Are the WHP Controllers and Loop Controller powered? Check 24 VAC to the
controllers.
•
Is the REC LED on the missing WHP Controller “flickering”? See WHP Controller
introduction for location of the REC LED. (see Figure 4-4)
•
Is the COMM LED on the WHP Controller blinking an error code? See the Blink
Code chart. (see Figure 4-6)
•
Are Comm Loop voltages correct at the missing unit? See Comm Loop troubleshoot-
ing guide starting on page 4-24.
Содержание Water Source Heat Pump
Страница 1: ...WHP Water Source Heat Pump Design Installation Operations Manual Revision 02A...
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 22: ...Section 1 WattMaster WHP 1 16 Design Guide Notes...
Страница 48: ......
Страница 80: ...Section 3 WattMaster WHP 3 32 Programming Notes...
Страница 125: ...WattMaster WHP Section 4 Start Up and Troubleshooting 4 43 Notes...