WattMaster WHP
Section 4
Start-Up and Troubleshooting
4-9
3.0 Loop Controller
Overview
3.1
How It Works
3.1.1
Initialization
On system powerup LED2 remains extinguished for five seconds. After this delay, the
LED2 will blink out the address of the controller (Address Switch Setting). The LED2
will then extinguish for another five seconds and then the LED2 will begin blinking a
diagnostic code every ten seconds. This code is described in the troubleshooting section.
The duration of a powerup initialization sequence is roughly thirty seconds.
During this initialization period, the controller retrieves all operating setpoints from its
non-volatile EEPROM memory and initializes all outputs to an OFF condition.
3.1.2
Operating Summary
There is a standard set of operating instructions that are continuously performed over and
over during normal Loop Controller operations. They are listed below.
a
Read analog inputs for temperatures, pressures and binary contact closures
b
Checks for new setpoints from System Manager or Prism Software and keeps the
status values updated for these interfaces.
c
Looks for “request to run” broadcast from any installed WHP Controller or from
an on-board binary input.
d. Set all outputs to match calculations for heat rejection or addition.
e. Store data in internal trend log if ready for another log
f.
Broadcasts the operating commands to all WHP Controllers.
g.
Tests for lead/lag pump changeover if both pumps are off.
h.
Repeat steps a-g continuously
Содержание Water Source Heat Pump
Страница 1: ...WHP Water Source Heat Pump Design Installation Operations Manual Revision 02A...
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 22: ...Section 1 WattMaster WHP 1 16 Design Guide Notes...
Страница 48: ......
Страница 80: ...Section 3 WattMaster WHP 3 32 Programming Notes...
Страница 125: ...WattMaster WHP Section 4 Start Up and Troubleshooting 4 43 Notes...