Section 3
WattMaster WHP
3-22
Programming
3) Reset Pumps
WSHPRV 1 v2.03
Tripped Pump Reset
Reset Mode: Disabled
Use Left/Right Arrow
If one of your heat pumps has tripped off, it can be manually
reset from the following screen. You will have entered the
Unit ID to access the WHP Menu screen, so that is the unit
that will receive this reset command. If you don’t want to
send the command, select the Disabled message with the
arrow keys. If you do want to send the command, select the
Enabled message with the arrow keys and then press the
Enter button. This command will automatically clear itself
when the WHP detects it and performs the reset.
There are two methods of resetting:
1.
Relay #4, on the WHP will activate with the reset
command and can be wired to provide the reset
action.
2.
The compressor relay will be cycled off. On
newer heat pumps, this is all that is required to
reset the operation.