WattMaster WHP
Section 4
4-42
Start-Up and Troubleshooting
5.6 Pressure Sensor Voltage Chart
PRESSURE
PSI
CURRENT
MILIAMPS
VOLTAGE AT
INPUT
VDC*
0
4.00
1.00
1
4.32
1.08
2
4.64
1.16
3
4.96
1.24
4
5.28
1.32
5
5.60
1.40
6
5.92
1.48
7
6.24
1.56
8
6.56
1.64
9
6.88
1.72
10
7.20
1.80
11
7.52
1.88
12
7.84
1.96
13
8.16
2.04
14
8.48
2.12
15
8.80
2.20
16
9.12
2.28
17
9.44
2.36
18
9.76
2.44
19
10.08
2.52
20
10.40
2.60
21
10.72
2.68
22
11.04
2.76
23
11.36
2.84
24
11.68
2.92
25
12.00
3.00
26
12.32
3.08
27
12.64
3.16
28
12.96
3.24
29
13.28
3.32
30
13.60
3.40
31
13.92
3.48
32
14.24
3.56
33
14.56
3.64
PRESSURE
PSI
CURRENT
MILIAMPS
VOLTAGE AT
INPUT
VDC*
34
14.88
3.72
35
15.20
3.80
36
15.52
3.88
37
15.84
3.96
38
16.16
4.04
39
16.48
4.12
40
16.80
4.20
41
17.12
4.28
42
17.44
4.36
43
17.76
4.44
44
18.08
4.52
45
18.40
4.60
46
18.72
4.68
47
19.04
4.76
48
19.36
4.84
49
19.78
4.92
50
20.00
5.00
*Notes
:
1.
Use the voltage column to compare the
meter voltage with the sensor connected to
the controller and with the controller pow-
ered.
2.
Read voltage with meter set on DC volts.
Place the “-”(minus) lead on GND terminal
and the “+”(plus) lead on the sensor input
terminal being investigated.
3.
If the voltage is less than 0.05 VDC, then
the sensor or wiring is “shorted” or “open”
Содержание Water Source Heat Pump
Страница 1: ...WHP Water Source Heat Pump Design Installation Operations Manual Revision 02A...
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 22: ...Section 1 WattMaster WHP 1 16 Design Guide Notes...
Страница 48: ......
Страница 80: ...Section 3 WattMaster WHP 3 32 Programming Notes...
Страница 125: ...WattMaster WHP Section 4 Start Up and Troubleshooting 4 43 Notes...