WattMaster WHP
Section
3
Programming
3-23
Loop Controller Status
Loop Controller Status Menu
From the main menu screen select MENU on the keypad. Then select “View Status
Only” (keypad #1) and finally enter the loop and zone number for the desired unit.
As the screen above shows, there are two areas of status available for the Loop
Controller. Menu item #1 accesses all the status screens for the Loop Controller. Menu
item #2 accesses the alarms for the Loop Controller. “Menu” can be selected to access the
Setpoints screens.
Loop Controller Status
Screens
If you selected menu item #1, View Status Only, and you entered the Unit ID of the Loop
Controller, the following Status Screens are available.
Status Screen #1
1) View Status Only
2) View Alarms
Menu) Setpoints
ESC) To Exit
Line 2 -
Current operating Mode:
OCCUPIED
UNOCCUPIED
Line 3 -
Current Return Water Temperature
Line 4 -
Current Supply Water Temperature
Loop Control v1.06
OCCUPIED
Return Temp: xx.x
°
F
Supply Temp: xx.x
°
F