Control wiring
Never apply mains power to the D-connectors. Apply the correct signals to
the pins shown. Limit signals to the maximum values shown. Do not apply
voltage across other pins. Permanent damage, not covered by warranty, may
result.
Keep 4-20mA and low voltage signals separate from mains power. Use
separate glanded input cables. Following best EMC practice and use of
shielded glands is recommended.
Ensure that multi-strand wires are terminated with a crimp suitable to the
wire diameter, (applies to NEMA or SCADA model connections only, not sub-D
connector type terminations). Failure to do so may result in electric shock.
13.1
Upper D-connector
Recommended control cable: 7/0.2mm 24AWG screened. Cable screen should be earthed with a 360 deg
connection to a conductive back-shell. This will be connected to pump mains EARTH via the D connector
body. Mains Earth is also available on pin 1 Upper D and pin 13 Lower D.
Functional
earth
Leak
Signal
ground
(0V)
Signal
ground
(0V)
Upper D-connector
13.2
PROFIBUS
PROFIBUS 9 way D Connector. Cable suitable for use in a PROFIBUS DP installation must be used.
EARTH
24
m-630bpn-en-08
Содержание 630 Bp
Страница 21: ...1 2 m 630bpn en 08 21...
Страница 46: ...14 7 Network topology Star network Ring network 46 m 630bpn en 08...
Страница 105: ...22 5 Flow Sensor Reading The flow sensor value can be read via the Flow sensor reading screen m 630bpn en 08 105...
Страница 107: ...Press SELECT to choose an option Press EXIT to return to the screen from where the MENU was called m 630bpn en 08 107...
Страница 130: ...24 Help 24 1 Help Select Help from the main menu to access the help screens 130 m 630bpn en 08...
Страница 150: ...Number Spare Description 8 TT0005 10mm 3 8in spanner 9 MRA3026A Track assembly 150 m 630bpn en 08...