2 .8 .2 Connecting to the DHW circuit
Install dielectric fittings and DHW pipes on the tank
(see
figure 23
). Insulate DHW pipes with included
insulation.
"
Be sure to put the DHW sensor at the bottom of
the thermowell DHW.
Required:
On the cold water inlet, place a safety unit
rated (from 7 to 10 bars - required by local regulations)
and connected to a drain pipe leading to the sewers.
Operate the safety unit according to manufacturer's
specifications.
There should be no valve between the safety unit and
the tank.
We recommend that a thermostatic mixer be placed on
the hot water outlet.
Right DHW outlet of the HP
Left DHW outlet of the HP
Each side DHW outlet of the HP
55 mm
figure 23 - DHW pipes mounting
figure 24 - DHW outlet
Installation and operating manual "1585 - EN"
- 25 -