Line
Function
Setting range
or display
Setting
increment
Basic
setting
Cooling circuit 1
If the installation is fitted with the cooling kit (Only with the cooling kit option).
901
U
Operating mode
Off, Automatic
Off
902
U
Comfort cooling setpoint
17 40 °C
0,5 °C
24 °C
907
U
Release
24h/day, Time program HC,
Time program 5 / Refresh
Time
program 5
If the installation is fitted with a DHW tank, set the parameter 907 to " Time program 5 / Cooling"
(In order to activate cooling only during the day and leave the DHW system to operate during the night).
908
I
Flow temp setp at OT° 25°C
6 35 °C
0,5 °C
20 °C
909
I
Flow temp setp at OT° 35°C
6 35 °C
0,5 °C
16 °C
912
I
Cooling limit at OT°
8 35 °C
0,5 °C
24 °C
913
S
Lock time at end of heating
8 100
1 h
24 h
918
S
Summer comp start at OT°
20 50 °C
1 °C
26 °C
919
S
Summer comp end at OT°
20 50 °C
1 °C
40 °C
920
S
Summer comp setp increase
1 10 °C
1 °C
4 °C
923
S
Flow temp setp min OT° 25°C
6 35 °C
0,5 °C
18 °C
924
S
Flow temp setp min OT° 35°C
6 35 °C
0,5 °C
18 °C
928
S
Room influence
1... 100 %
1 %
80 %
If the installation is fitted with a room thermostat:
This function enables you to choose the ambient temperature's influence on the setting.
If no value is entered, the setting is made based on the temperature control.
If the parameter is set at 100%, the setting is only based on the ambient temperature.
932
S
Room temp limitation
0,5... 4 °C
0,5 °C
0,5 °C
938
S
Mixing valve decrease
0 20 °C
1 °C
0 °C
941
S
Actuator running time
30... 873 s
1 s
240 s
945
S
Mixing valve in heating mode
Control, Open
Control
946
S
Lock time dewpoint limiter
10... 600 min
10 min
60 min
963
S
With prim contr / system pump
No, Yes
No*
*Basic setting : 1 circuit = No ; 2 circuits = Yes.
969
S
Operating mode changeover
No, Off, Automatic
Off
Heating adjustment, Circuit 2
Only with the 2nd circuit kit option (If the installation consists of 2 heating circuits).
1010
U
Comfort setpoint
Reduced setpoint…
Comfort setpoint maximum
0,5 °C
20 °C
1012
U
Reduced setpoint
Frost protection setpoint…
Comfort setpoint
0,5 °C
19 °C
1014
U
Frost protection setpoint
4 °C… Reduced setpoint
0,5 °C
8 °C
1016
S
Comfort setpoint maximum
Comfort temp... 35 °C
1 °C
28 °C
1020
I
Heating curve slope
0,1... 4
0,02
0,5
(see chapter
3.4.3, page 42
&
figure 41, page 41
)
1021
I
Off-set of the heating curve (
figure 42, page 41
)
-4,5... 4,5 °C
0,5 °C
0 °C
1030
I
Summer / Winter heating limits
8 30 °C
0,5 °C
18 °C
When the average of the outside temperatures over the past 24 hours reaches 18°C, the regulator switches off the heating
(as an economy measure). During summer mode, the display shows "Eco". This function is only active in automatic mode.
1040
S
Flow temp setpoint min
8 70 °C
1 °C
17 °C
(with dynamic radiator, adjust from 30 to 35°C)
Installation and operating manual "1585 - EN"
- 47 -
Air to Water Heat Pump (Split integrated DHW type)
Содержание WO A060LDC Series
Страница 19: ... Installation and operating manual 1585 EN 19 Air to Water Heat Pump Split integrated DHW type ...
Страница 70: ... Installation and operating manual 1585 EN Air to Water Heat Pump Split integrated DHW type 70 ...
Страница 71: ... Installation and operating manual 1585 EN 71 Air to Water Heat Pump Split integrated DHW type ...