WS1HR & WS1.25HR Manual 

Page 29

Installation Fitting Assemblies

The installation fi ttings connect to the control valve or the bypass valve using nuts that only require hand tightening. Hand tighten 
nut connections between control valve and installation fi ttings, control valve and bypass valve, and bypass valve and installation 
fi ttings allow for easy serviceability. Do not use a pipe wrench to tighten nuts on installation fi ttings. Hand tighten only. 

The split ring retainer design holds the nut on and allows load to be spread over the entire nut surface area, reducing the chance for 
leakage. The split ring design, incorporated into the installation fi ttings allows approximately 2 degrees off axis alignment to the 
plumbing system. The installation fi ttings are designed to accommodate minor plumbing misalignments but are not designed to 
support the weight of a system or the plumbing.

When assembling the installation fi tting package, connect the fi tting to the plumbing system fi rst and then attach the nut, split ring 
and o-ring. Heat from soldering or solvent cements may damage the nut, split ring or o-ring. Solder joints should be cool and solvent 
cements should be set before installing the nut, split ring and o-ring. Avoid getting primer and solvent cement on any part of the o-
rings, split rings, bypass valve or control valve. Solvent cements and primers should be used in accordance with the manufacturer’s 
instructions.

Slip the nut onto the fi tting fi rst, then the split ring second and the o-ring last. Hand tighten the nut. If the fi tting is leaking tightening 
the nut will not stop the leak. Remove the nut, remove the fi tting, and check for damage or misalignment of the o-ring. 

Do not use pipe dope or other sealant on threads. 

Use tefl on tape on threaded inlet, outlet and drain fi ttings. 

Tefl on tape is not 

necessary on the nut connection or caps because of o-ring seals.

Do not use Vaseline, oils, or other unacceptable lubricants on o-rings. A silicone lubricant may be used on black o-rings.

Bypass Valve

The bypass valve easily connects to the control valve body using nuts that only require hand tightening. Hand tighten nut 
connections between control valve and fi ttings, control valve and bypass valve, and bypass valve and installation fi ttings allow 
for easy serviceability. The split ring retainer design holds the nut on and allows load to be spread over the entire nut surface 
area, reducing the chance for leakage. The split ring design incorporated into the bypass allows approximately 2 degrees off axis 
alignment to the plumbing system. The bypass is designed to accommodate minor plumbing misalignments but is not designed to 
support the weight of a system or the plumbing.

Avoid getting primer and solvent cements on any part of the o-rings or split rings, bypass valve or control valve. Do not use pipe 
dope or other sealant on threads. Tefl on tape is not necessary on the caps because of o-ring seals.

Do not use Vaseline, oils, or other unacceptable lubricants on o-rings. A silicone lubricant may be used on black o-rings.

Mixing Valve

The mixing valve is an option on the control valve. If the control valve is ordered with a mixing valve it will be installed in the 
control valve assembly process.

To adjust the blended water, close the mixing valve. Open a water faucet to the desired fl ow rate. Open the mixing valve until the 
desired hardness is reached. Close the faucet.

Note: The use of the mixing valve requires modifi cation to the valve body. These modifi cations should not be done in the fi eld.

Содержание WS1HR

Страница 1: ...Valve Series Model WS1 25HR Operation and Instruction Manual for OEM Only Please Note This operation and instruction manual is for the training of the OEM and for the OEM to use to train their custome...

Страница 2: ......

Страница 3: ...Valve History 27 Installation 28 Drawings and Part Numbers 30 Front Cover and Drive Assembly 31 WS1HR Drive Cap Assembly Downflow Piston Upflow Piston Regenerant Piston and Spacer Stack Assembly 32 W...

Страница 4: ...nlet outlet and drain fittings Teflon tape is not necessary on the nut connection or caps because of o ring seals After completing any valve maintenance involving the drive assembly or the drive cap a...

Страница 5: ...kPa drop Backwash flow rate 1 25 includes bypass 30 gpm 113 5 lpm 25 psig 172 kPa drop Minimum Maximum Operating Pressures 20 psi 138 kPa 125 psi 862 kPa Minimum Maximum Operating Temperatures 40 F 4...

Страница 6: ...ers and pliers Disassembly for servicing takes much less time than comparable products currently on the market Control valve installation is made easy because the distributor tube can be cut above to...

Страница 7: ...he regeneration The user cannot cancel this request except by resetting the control by pressing NEXT and REGEN buttons simultaneously for 3 seconds The WS1HR WS1 25HR control valves consist of the fol...

Страница 8: ...ill The PC board determines the position of the piston by counting pulses produced when the piston is moved An optical sensor looking at one of the reduction drive gears generates these pulses Each cy...

Страница 9: ...ation plug in UP location regeneration upflow WS1HR only upflow option is for softeners only install injector in UP location plug in other hole location no regenerant WS1HR WS1 25HR both the DN and UP...

Страница 10: ...e flow control can be installed in the standard drain line elbow which accommodates 5 8 polytube or NPT drain line connections The optional nut and polytube insert for the drain line elbow is designed...

Страница 11: ...alves with water meters provide a wider variety of useful information see OEM General Instructions for list of information A unique feature of this control valve is the ability to display actual water...

Страница 12: ...aced if service is required The bypass consists of two interchangeable plug valves that are operated independently by red arrow shaped handles The handles identify the flow direction of the water The...

Страница 13: ...WS1HR WS1 25HR Manual Page 13 Figure 3 Figure 4 Figure 1 Figure 2...

Страница 14: ...clear the service call reminder press the and buttons simultaneously while CALL is displayed When desired all information in Diagnostics may be reset to zero when the valve is installed in a new locat...

Страница 15: ...ntrol Valve to have no hard water bypass Selecting the use of an outside signal to initiate a regeneration Selection only matters if a connection is made to the two pin connector labeled DP SWITCH loc...

Страница 16: ...eing used and that the injector or injector plug s are in the correct locations See Compliance Table in Service Instructions under Injector Cap Screen Injector Plug and Injector section and Figure 6 P...

Страница 17: ...to previous step Cycle Options Units Lower Upper Limit Backwash Minutes 1 to 120 Rinse fast Minutes 1 to 120 dn Brine combination of brining and slow rinse Minutes 1 to 180 UP Brine combination of bri...

Страница 18: ...the beginning of a regeneration and then deactivates after a set period of time The start of regeneration is defined as the first backwash cycle or Dn brine cycle which ever comes first Set Gal Soften...

Страница 19: ...e capacity not automatically estimated Regeneration occurs immediately when gallons capacity reaches 0 Time of regeneration will not be allowed to be set because regeneration will always occur when ga...

Страница 20: ...xample is BACKWASH using the or button Press NEXT to go to Step 4F Press REGEN to return to previous step Step 4F Select the time for the second cycle which in this example is dn BRINE using the or bu...

Страница 21: ...efined as the first backwash cycle or Dn brine cycle which ever comes first Set Gal Softening on Relay activates after a set number of gallons have been used while in service and then deactivates afte...

Страница 22: ...ty not automatically estimated Regeneration occurs at the next Regen Set Time when gallons capacity reaches 0 or the specified number of days between regenerations is reached Any number On O oFF Reser...

Страница 23: ...n that day even if sufficient volume of water were not used to call for a regeneration Set Day Override using or buttons number of days between regeneration 1 to 28 or oFF See Table 8 for more detail...

Страница 24: ...s and will also increase the volume used impacting the recorded values in Diagnostics Steps 3D 4D and 5D and Valve History Step 4VH The third display shows the current treated water flow rate through...

Страница 25: ...ivate if REGEN button is pressed To initiate a manual regeneration immediately press and hold the REGEN button for three seconds The system will begin to regenerate immediately The request cannot be c...

Страница 26: ...be pressed to move backwards in the day series Press the NEXT button at any time to go to Step 5D Press REGEN to return to previous step STEP 5D Volume 63 day usage history This display shows day 1 f...

Страница 27: ...isplay shows the total days since startup Press the NEXT button to go to Step 3VH Press REGEN to return to previous step STEP 3VH Regenerations total number since start up This display shows the total...

Страница 28: ...n line flow control use an elbow fitting that does not contain a hole If the drain line is a 5 8 flexible polytube slide the nut onto the polytube then place the polytube insert into the end of the po...

Страница 29: ...r misalignment of the o ring Do not use pipe dope or other sealant on threads Use teflon tape on threaded inlet outlet and drain fittings Teflon tape is not necessary on the nut connection or caps bec...

Страница 30: ...Page 30 WS1HR WS1 25HR Manual Drawings and Part Numbers...

Страница 31: ...and Description Relay Socket SH3B 05C 3 pole finger safe rail mount socket Relay RH2LB U AC12V 12vac DPDT magnetic latching relay The relay supplies 2 sets of dry contacts for user applications The wi...

Страница 32: ...Plate 1 4a V3011 WS1 Piston Downflow ASY 1 4b V3011 01 WS1 Piston Upflow ASY 5 V3174 WS1 Regenerant Piston 1 6 V3135 O ring 228 1 7 V3180 O ring 337 1 8 V3105 O ring 215 Distributor Tube 1 Not Shown V...

Страница 33: ...ive Back Plate 1 4 V3407 WS1 5 Piston Downflow ASY 1 5 V3174 WS1 Regenerant Piston 1 6 V3135 O ring 228 1 7 V3180 O ring 337 1 8 V3358 O ring 219 Distributor Tube Opening 1 32 1 V3357 O ring 218 Distr...

Страница 34: ...ASY E WHITE V3010 1F WS1 INJECTOR ASY F BLUE V3010 1G WS1 INJECTOR ASY G YELLOW V3010 1H WS1 INJECTOR ASY H GREEN V3010 1I WS1 INJECTOR ASY I ORANGE V3010 1J WS1 INJECTOR ASY J LIGHT BLUE V3010 1K WS...

Страница 35: ...y 1 V3195 01 WS1 Refill Port Plug Asy This part is required for backwash only systems 2 H4615 Elbow Locking Clip 1 3 JCP P 6 Polytube insert 3 8 1 4 JCPG 6PBLK Nut 3 8 1 5 H4613 Elbow Cap 3 8 1 6 V316...

Страница 36: ...162 010 WS1 DLFC 1 0 gpm for V3162 013 WS1 DLFC 1 3 gpm for V3162 017 WS1 DLFC 1 7 gpm for V3162 022 WS1 DLFC 2 2 gpm for V3162 027 WS1 DLFC 2 7 gpm for V3162 032 WS1 DLFC 3 2 gpm for V3162 042 WS1 DL...

Страница 37: ...FTG Adapter 1 1 5 V3163 0 ring 019 1 6 V3150 WS1 Split Ring 1 7 V3151 WS1 Nut 1 QC 1 8 V3105 O ring 215 1 9 V3190 090 WS1 DLFC 9 0 gpm for 1 One DLFC must be used if 1 fitting is used V3190 100 WS1 D...

Страница 38: ...1 2 V3003 WS1 Meter ASY 1 3 V3118 01 WS1 Turbine ASY 1 4 V3105 0 ring 215 1 5 V3003 01 WS1 Meter Plug ASY 1 6 V3013 Mixing Valve Optional Order number V3003 includes V3118 01 WS1 Turbine ASY and V3105...

Страница 39: ...1 Nut 1 Quick Connect 2 2 V3150 WS1 Split Ring 2 3 V3105 O Ring 215 2 4 V3188 WS1 Fitting 1 Brass Sweat Assembly 2 Order No V3007 03 Description WS1 Fitting Brass Sweat Assembly Drawing No Order No De...

Страница 40: ...er No Description Quantity 1 V3151 WS1 Nut 1 Quick Connect 2 2 V3150 WS1 Split Ring 2 3 V3105 O Ring 215 2 4 V3361 WS1 Fitting 1 1 4 Plastic Male BSPT 2 2 1 4 3 Drawing No Order No Description Quantit...

Страница 41: ...5 WS1 Bypass 1 Rotor 2 5 V3146 WS1 Bypass Cap 2 6 V3147 WS1 Bypass Handle 2 7 V3148 WS1 Bypass Rotor Seal Retainer 2 8 V3152 O ring 135 2 9 V3155 O ring 112 2 10 V3156 O ring 214 2 Not Shown Order No...

Страница 42: ...Page 42 WS1HR WS1 25HR Manual Flow Diagrams Service and Backwash...

Страница 43: ...WS1HR WS1 25HR Manual Page 43 Flow Diagrams Downflow and Upflow WS1HR Only...

Страница 44: ...Page 44 WS1HR WS1 25HR Manual Flow Diagrams Rinse and Fill...

Страница 45: ...tools are necessary to assemble or disassemble the valve the WS1 wrench shown in various positions on the valve may be purchased to aid in assembly or disassembly RRVHQV UDLQ 1XW Q 3RO WXEH SSOLFDWLR...

Страница 46: ...e bottom of the drive back plate Push the top of the drive bracket toward the two latches The drive bracket may have to be lifted slightly to let the threaded piston rod pass through the hole in the d...

Страница 47: ...all wording then flash the software version and then reset the valve to the service position Drive Cap Assembly Main Piston and Regenerant Piston The drive assembly must be removed to access the drive...

Страница 48: ...thout tools by using thumb and forefinger Inspect the black o rings and clear lip seals for wear or damage Replace the entire stack if necessary Do not disassemble the WS1HR or WS1 25HR stack The spac...

Страница 49: ...the side of the drive assembly Reattach the drive assembly and the water meter and power plugs THIS WATER METER SHOULD NOT BE USED AS THE PRIMARY MONITORING DEVICE FOR CRITICAL HEALTH EFFECT APPLICATI...

Страница 50: ...valve until the desired hardness is reached Close the faucet Bypass Valve The working parts of the bypass valve are the rotor assemblies that are contained under the bypass valve caps Before working o...

Страница 51: ...ration time option e Control valve set at NORMAL on 0 e Check control valve set up procedure regeneration time option 5 ERROR followed by code number Error Code 1001 Unable to recognize start of regen...

Страница 52: ...held a AC Adapter unplugged a Connect AC Adapter b No electric power at outlet b Repair outlet or use working outlet c Broken drive gear or drive cap assembly c Replace drive gear or drive cap assemb...

Страница 53: ...tor Tube Opening Identification 4D 2 3 Black Plug 1 25 1 25 Spacer Color Grey Note The WS1HR HS downflow piston is a solid amber color The WS1HR HS upflow piston is black and amber Grey Plug 1 5 Space...

Страница 54: ...Page 54 WS1HR WS1 25HR Manual...

Страница 55: ...WS1HR WS1 25HR Manual Page 55...

Страница 56: ...Page 56 WS1HR WS1 25HR Manual...

Страница 57: ...WS1HR WS1 25HR Manual Page 57...

Страница 58: ...Page 58 WS1HR WS1 25HR Manual...

Страница 59: ...WS1HR WS1 25HR Manual Page 59...

Отзывы: