Page 18
WS1HR & WS1.25HR Manual
Step 9S – Set Regeneration Time Options using the
▼
or
▲
button. If value is set to:
• “NORMAL” means regeneration will occur at the preset time;
• “on 0” means regeneration will occur immediately when the gallons capacity reaches 0 (zero); or
• “ on 0” means regeneration will occur at one of the following:
— the preset time when the gallons capacity falls below the reserve or the specifi ed number of days between
regenerations is reached, whichever comes fi rst; or
— after 10 minutes of no water usage when the gallon capacity reaches 0 (zero).
See Table 8 for more detail. Press NEXT to go to Step 10S. Press REGEN to return to previous step.
STEP 8S
Step 8S – Set Volume Capacity using the
▼
or
▲
button. If value is set to:
• “AUTO” capacity will be automatically calculated and reserve capacity will be automatically estimated;
• “oFF” regeneration will be based solely on the day override set (see Installer Display Settings Step 3I); or
• as a number regeneration initiation will be based off the value specifi ed.
If “oFF” or a number is used, hardness display will not be allowed to be set in Installer Display Settings Step 2I.
See Table 8 for more detail. Press NEXT to go to Step 9S. Press REGEN to return to previous step.
STEP 9S
STEP 13S
Step 13S: Set the Service Call Indicator by using the
▲
or
▼
buttons. Range is
in ¼ of a year increments from 0.25 to 9.75 years. Selecting OFF will disable this
feature. Press NEXT to exit OEM Softener System Setup. Press REGEN to return
to previous step.
RETURN TO NORMAL MODE
Step 10S: Set Relay operation using the
▲
or
▼
button. The choices are:
• Set Time on: Relay activates after a set time at the beginning of a regeneration and then deactivates after a set
period of time. The start of regeneration is defi ned as the fi rst backwash cycle or Dn brine cycle, which ever comes
fi rst.
• Set Gal Softening on: Relay activates after a set number of gallons have been used while in service and then
deactivates after a set period of time or after the meter stops registering fl ow, whichever comes fi rst.
• Set Gal Softening Regen on: Relay activates after a set number of gallons have been used while in service or dur-
ing regeneration and then deactivates after a set period of time or after the meter stops registering fl ow, whichever
comes fi rst.
• Set Off: If set to Off, Steps 11S and 12S will not be shown.
Press NEXT to go to Step 11S. Press REGEN to return to previous step.
STEP 10S
STEP 11S
Step 11S: Set Relay Actuation Time or Gallons using the
▲
or
▼
buttons. The choices are:
• Relay Actuation Time: After the start of a regeneration the amount of time that should pass prior to activating
the relay. The start of regeneration is defi ned as the fi rst backwash cycle or Dn brine cycle, which ever comes fi rst.
Ranges from 1 second to 200 minutes.
• Relay Actuation Gallons: Relay activates after a set number of gallons have passed. Ranges from 1 to 50 gallons.
Press NEXT to go to Step 12S. Press REGEN to return to previous step.
STEP 12S
Step 12S: Set Relay Deactivate Time using the
▲
or
▼
buttons.
• If Set Time on is selected in Step 10S the relay will deactivate after the time set has expired. Ranges from 1
second to 200 minutes.
• If Set Gal Softening on or Set Gal Softening Regen on is selected in Step 10S the relay will deactivate after the
time set has expired or after the meter stops registering fl ow, whichever comes fi rst. Ranges from 1 second to 20
minutes.
Press NEXT to go to Step 13S. Press REGEN to return to previous step.
Содержание WS1HR
Страница 2: ......
Страница 13: ...WS1HR WS1 25HR Manual Page 13 Figure 3 Figure 4 Figure 1 Figure 2...
Страница 30: ...Page 30 WS1HR WS1 25HR Manual Drawings and Part Numbers...
Страница 42: ...Page 42 WS1HR WS1 25HR Manual Flow Diagrams Service and Backwash...
Страница 43: ...WS1HR WS1 25HR Manual Page 43 Flow Diagrams Downflow and Upflow WS1HR Only...
Страница 44: ...Page 44 WS1HR WS1 25HR Manual Flow Diagrams Rinse and Fill...
Страница 54: ...Page 54 WS1HR WS1 25HR Manual...
Страница 55: ...WS1HR WS1 25HR Manual Page 55...
Страница 56: ...Page 56 WS1HR WS1 25HR Manual...
Страница 57: ...WS1HR WS1 25HR Manual Page 57...
Страница 58: ...Page 58 WS1HR WS1 25HR Manual...
Страница 59: ...WS1HR WS1 25HR Manual Page 59...