Alarm (ALM) messages by PLC
Code
Message
Reason
Action
BAE0_1F51VOPR
ALM, Gen. Prot.,
Voltage restr.
Overcurrent I 7> (U)
Activation of back-
up protection to
disconnect the
generator if a system
fault has not been
cleared by other
protective devices
after a sufficient time
delay has elapsed
Check the prot. relay event recorder.
Check also for overcurrent indications
BAE0_1F000ALI ALM, Gen. protection
relay fault
Generator
protection relay
internal fault
Check the protection relay display or
use the protection relay program
(VAMPSet) to identify the problem
BAN0_1Q000ALI
ALM, Ground
disconnector (NP)
position error
Breaker open and
close signals active
OR none of the
signals active
Check the position contacts and
wiring
ZBB0_1P002AH
ALM, High diff.
pressure over gas filter
Gas regulating unit
gas filter clogged
Replace or clean the gas filter
ZBB0_1P003AH
ALM, High inlet gas
pressure
Too high gas supply
pressure to gas
regulating unit
Check gas supply line
ZBB0_1T001AH
ALM, High inlet gas
temperature
Too high gas supply
temperature to gas
regulating unit
Check gas supply line
SVH0_1M001MFI
ALM, HT cooling
water pump control
center fault
HT cooling water
pump motor
overcurrent/shortcircu
it tripped
Check the overcurrent/shortcircuit
relay
SVH0_1M001AFI
ALM, HT cooling
water pump
Start/Stop fault
HT cooling water
pump motor
activation is not
according to given
command
Check the functionality of the main
contactor, Check the wiring for
running information and start/stop
commands
ZBB0_1P003AL
ALM, Low inlet gas
pressure
Low high gas supply
pressure to gas
regulating unit
Check gas supply line
ZBB0_1T001AL
ALM, Low inlet gas
temperature
Low high gas supply
temperature to gas
regulating unit
Check gas supply line
VEA0_1L001AL
ALM, Low level in HT
expansion tank
Low water level in HT
expansion tank
Check the level in the HT expansion
level
VEA012L001AL
ALM, Low level in LT
expansion tank
Low water level in LT
expansion tank
Check the level in the LT expansion
level
SVL0_1M001MFI
ALM, LT cooling
water pump control
center fault
LT cooling water
pump motor
overcurrent/shortcircu
it tripped
Check the overcurrent/shortcircuit
relay
SVL0_1M001AFI
ALM, LT cooling
water pump
Start/Stop fault
LT cooling water
pump motor
activation is not
according to given
command
Check the functionality of the main
contactor, Check the wiring for
running information and start/stop
commands
34SG-200414-04
Operating Troubles
Содержание 41508
Страница 3: ......
Страница 12: ...Appendix B Welding Precautions 200147...
Страница 22: ...Fuel Lubricating Oil Cooling Water 34SG 200303 03...
Страница 29: ...A Ap pp pe en nd di ix x A A E En nv vi ir ro on nm me en nt ta al l H Ha az za ar rd ds s 2 20 00 03 32 21 1...
Страница 73: ...Maintenance Tools 32 9801...
Страница 115: ...Engine Block with Bearings Cylinder and Oil Sump 34SG 9701...