Alarm (ALM) messages by PLC
Code
Message
Reason
Action
NHA0_1A001VFI
ALM, Exh.vent.valve
fault
Exhaust ventilation
valve is not opened
within pre-defined
time from the
command
Check the ventilation valve
functionality, Check the valve open
indication switch, Check the air
supply
NHA0_1V001OPN ALM, Explosion relief
valve 1 open
Explosion relief valve
opened
Check the explosion relief valve
NHA0_1V002OPN ALM, Explosion relief
valve 2 open
Explosion relief valve
opened
Check the explosion relief valve
NHA0_1V003OPN ALM, Explosion relief
valve 3 open
Explosion relief valve
opened
Check the explosion relief valve
ZBB0_1A001ALI
ALM, Gas alarm level1
Gas alarm 10 % LEL
reached
Check the cause for the gas
leakage
ZBB0_1V015ALI
ALM, Gas shutoff
valve V015 leaking
Pressure raise
detected between
gas shutoff valves
V015 and V018
during gas leakage
test
Check the V015 gas shutoff valve for
leakages
ZBB0_1V015TFI
ALM, Gas shutoff
valve V015 stuck
Sufficient pressure
not detected at gas
shutoff valve V018
during gas leakage
test
Check the V015 gas shutoff valve
functionality
ZBB0_1V018ALI
ALM, Gas shutoff
valve V018 leaking
Pressure lost
between gas shutoff
valves V015 and
V018 during gas
leakage test
Check the V018 gas shutoff valve for
leakages
BAG0_1B001MFI
ALM, Gen anticond.
heater, control
center fault
Gen.
anticondensation
heater
overcurrent/shortcircu
it tripped
Check the overcurrent/shortcircuit
relay
BAG0_1B001AFI
ALM, Gen anticond.
heater, Start/Stop
fault
Gen.
anticondensation
heater activation is
not according to
given command
Check the functionality of the main
contactor, Check the wiring for
running information and start/stop
commands
BAE0_1Q000MCB
ALM, Gen. breaker
common alarm (MCB
open)
Generator MV panel
common alarm,
MCB tripped
Check the wiring
BAE0_1Q000ALI
ALM, Gen. breaker
position error
Breaker open and
close signals active
OR none of the
signals active
Check the position contacts and
wiring
BAE0_1E001ALI
ALM, Gen. breaker
SF6 pressure low
Leakage on breaker,
SF6 is leaking out
Check the SF6 pressure from local
gauge. If low, contact breaker
manufacturer, otherwise check
wiring and contacts.
CFC0_1S012TRI
ALM, Gen. breaker
tip circuit indication
Breaker trip circuit
activated
Check the separately informed
breaker trip cause
CFC0_1S012TRP
ALM, Gen. breaker
trip (Primary)
Breaker trip circuit
activated
Check the separately informed
breaker trip cause
Operating Troubles
34SG-200414-04
Содержание 41508
Страница 3: ......
Страница 12: ...Appendix B Welding Precautions 200147...
Страница 22: ...Fuel Lubricating Oil Cooling Water 34SG 200303 03...
Страница 29: ...A Ap pp pe en nd di ix x A A E En nv vi ir ro on nm me en nt ta al l H Ha az za ar rd ds s 2 20 00 03 32 21 1...
Страница 73: ...Maintenance Tools 32 9801...
Страница 115: ...Engine Block with Bearings Cylinder and Oil Sump 34SG 9701...