![WarmFlow WAH 100 Скачать руководство пользователя страница 9](http://html1.mh-extra.com/html/warmflow/wah-100/wah-100_installation-and-servicing-manual_3405183009.webp)
3.0
General Data
3.1
Technical Data
WAH MODEL
100/150
200/300
500/600
Output Range
kW
29.3-44.0
58.6-88.0
146.5-175.8
Nominal Heat
kW
52.4
102.3
206.9
Input (max)
Btu
178,800
349,000
705,900
Nominal Heat
kW
44.0
88.0
175.8
Output (max)
Btu
150,000
300,000
600,000
Nominal combustion efficiency
gross %
84
86
85
Burner Riello
RDB 2
G10
G20s
Head
LD3 A
G10
G20s
Flue Dia
mm
127
152
203
Flue Dia
in
5
6
8
Exit Flue Gas Mass Flow
Kg/h
Co2
%
11.0
11.0
11.0
Smoke Bacarach
0-1
0-1
0-1
0-1
NFGT
°
C
225
185
195
Nozzle
Danfoss or Delevan
(Kerosine)
1.25 x 60
°
S
2.5 x 60
°
S
—
Pump
Bar
10
9
—
Pressure
psi
145
130
—
Nozzle
Danfoss or Delevan
(Gas Oil)
1.0 x 60
°
S
2.0 x 60
°
S
4.0 x 60
°
S
Pump
Bar
13
12.5
13.0
Pressure
psi
190
180
190
Approx Fuel
L/h
5.2
10.1
20.4
Flow Rate
Gal/h
1.14
2.22
4.49
Fan Motor
kW
0.37
1.1
2.2
Motor Speed
rpm
1,440
1,440
1,440
Running Current
Amps
1.8
4.8
5.6
Electrical Supply at 50hz
Volts 230
±
6% 1PH 230
±
6% 1PH 400
±
6% 1PH
Fuse Rating (per phase)
Amps
5
8
16
Temp Rise
°
C
40
42
40
Inlet Air Flow @ 15 C
CFM
1,590
2,755
7,355
M
3
/h
2,700
4,680
12,500
No of Discharge Hoods
2
2
4
Fan Speed (Nominal)
rpm
650
900
925
Weight (including burner)
Kg
195
360
680