6.3
Air Damper Adjustment
The setting is purely indicative.
Each installation however, has its own unpredictable working conditions: actual nozzle
output; positive or negative pressure in the combustion chamber, the need of excess
air, etc.
All these conditions may require a different air-damper setting, which should be checked
and set during commissioning.
6.4
Electrode Setting
Before assembling or removing the nozzle,
loosen the screw (A) and move the electrodes
away from the nozzle.
6.5
Burner Start-up Cycle
Attention
Before working at the
electrodes ensure that
the power supply is
switched off.
~ 12s
Thermostat
Motor
Ignition transformer
Valve
Flame
Lock-out lamp
~ 12s
Normal
Lock-out due to failure to light
~ 5s
Page 23