background image

6

7

Always route low voltage (sensor) signals with at least a 6” (15 cm) separation from AC voltage wiring. 

The 

electrodeless conductivity sensor 

should be placed as close to the controller as possible, to a maximum distance 

of 120 ft. (37 m). Less than 20 ft. (6 m) is recommended.. The cable must be shielded from background electrical noise. 

Always route low voltage (sensor) signals with at least a 6” (15 cm) separation from AC voltage wiring. These sensors 

are affected by the geometry and conductivity of their surroundings, so either maintain 6 inches (15 cm) of sample 

around the sensor or ensure that any nearby conductive or nonconductive items are consistently positioned. Do not install 

the sensor in the path of any electrical current that may be flowing in the solution, as this will shift the conductivity reading.

IMPORTANT:  

To avoid damaging the female pipe threads on the supplied plumbing parts, use no more than 3 wraps 

of PTFE tape and thread into the pipe FINGER tight only!  DO NOT use any pipe dope, plumber’s putty or other 

sealing products that containdiacetone alcohol, as these attack the flow switch plastic!  Use PTFE tape ONLY!

Boilers:

The 

conductivity sensor 

should be placed as close to the controller as possible, to a maximum distance of 250 ft. 

(76m). The cable MUST be shielded from background electrical noise.  Use 24 AWG cable.

Important Boiler Installation Notes: (see figures 3 and 4)

1.  Make sure the minimum water level in the boiler is at least 4-6 inches (10-15 cm) above the skimmer blowdown 

line. If the skimmer line is closer to the surface, it is likely that steam will be drawn into the line instead of boiler 

water. The skimmer line must also be installed above the highest tube. 

2. 

Maintain a 3/4 inch minimum pipe ID with no flow restrictions from the tap for the boiler skimmer blowdown 

line to the electrode. If the ID is reduced below 3/4 inch, then flashing will occur beyond that point and the con

-

ductivity reading will be low and erratic. Minimize the usage of tees, valves, elbows or unions between the boiler 

and the electrode. 

3.  A manual shut off valve should be installed so that the electrode can be removed and cleaned. This valve must be 

a full port valve in order to avoid a flow restriction. 

 

4.  Keep the distance between the tap for the boiler skimmer line to the electrode as short as possible, to a maximum 

of 10 feet (3m). 

5.  Mount the electrode in the side branch of a tee in a horizontal run of pipe. This will minimize entrapment of 

steam around the electrode and will allow any solids to pass through. 

6. 

There MUST be a flow restriction after the electrode and/or control valve in order to provide back pressure. This 

flow restriction will be either a flow control valve or an orifice union. The amount of the flow restriction will 

affect the blowdown rate as well, and should be sized accordingly. 

7.  Install the motorized ball valve or solenoid valve per the manufacturer’s instructions. 

For best results, align the hole in the conductivity electrode such that the direction of water flow is through the hole.

Guide to Sizing Blowdown Valves and Orifice Plates

1.  Determine the Rate of Steam Production in Pounds per Hour:

Either read off the boiler name plate (water-tube boilers) or Calculate from horsepower rating (fire-tube boilers):

HP x 34.5 = lbs./hr. Example: 100 HP = 3450 lbs./hr

2.  Determine the Concentration Ratio (BASED ON FEEDWATER)

A water treatment chemical specialist should determine the desired number of cycles of concentration. This is the  

ratio of TDS in the boiler water to TDS in the feedwater. Note that feedwater means the water that is fed to the   

boiler from the deaerator and includes makeup water plus condensate return.

Example: 10 cycles of concentration has been recommended

3.  Determine the Required Blowdown Rate in Pounds Per Hour

Blowdown Rate = Steam Production / (Concentration Ratio –1)

4 mA Value

0

30,000

20 mA Value

0

30,000

Hand Output

0%

100%

Set Point

0

30,000

Proportional Band

0

30,000

Minimum Output

0%

100%

Maximum Output

0%

100%

Off Mode Output (Proportional, PID, Flow Prop modes)

0 mA

21 mA

Pump Capacity (Flow Prop mode)

0 gal/hour or l/hour

10,000 gal/hour or l/hour

Pump Setting (Flow Prop mode)

0%

100%

Specific Gravity (Flow Prop mode)

0 g/ml

9.999 g/ml

Target (Flow Prop mode)

0 ppm

1,000,000 pm

Error Output

0 mA

21 mA

Configuration settings

Low Limit

High Limit

Local Password

0000

9999

Alarm Delay

0:00 minutes

59:59 minutes

  

3.0  UNPACKING & INSTALLATION

3.1  Unpacking the unit

Inspect the contents of the carton. Please notify the carrier immediately if there are any signs of damage to the 

controller or its parts. Contact your distributor if any of the parts are missing.  The carton should contain a W100 

series controller and an instruction manual.  Any options or accessories will be incorporated as ordered.

3.2  Mounting the electronic enclosure

The controller is supplied with mounting holes on the enclosure. It should be wall mounted with the display at eye level, 

on a vibration-free surface, utilizing all four mounting holes for maximum stability.  Use M6 (1/4” diameter) fasteners 

that are appropriate for the substrate material of the wall.  The enclosure is NEMA 4X (IP65) rated. The maximum 

operating ambient temperature is 131°F (55°C); this should be considered if installation is in a high temperature 

location. The enclosure requires the following clearances:

 

Top:   

2” (50 mm)

 

Left:   

8” (203 mm) (not applicable for prewired models)

 

Right:   

4” (102 mm)

 

Bottom: 

7” (178 mm)

3.3 Installation

Once the controller is mounted, the metering pumps may be located at any distance from the controller. 

Plumbing

The W100 se

ries controllers can be supplied with a flow switch manifold designed to provide a continuously flowing 

sample of cooling water to the sensors. Please refer to Figures 2 through 6 below for some typical installation drawings.

Cooling Towers:

Tap off the discharge side of the recirculation pump to provide a minimum flow of 1 gallon per minute past the sensor. 

The sample must flow into the bottom of the manifold in order to close the flow switch, and return to a point of 

lower pressure in order to ensure flow. Install an isolation valve on both sides of the manifold to stop flow for 

sensor maintenance.

The

 contacting conductivity sensor 

should be placed as close to the controller as possible, to a maximum distance of 

250 ft. (76 m). Less than 25 ft. (8 m) is recommended. The cable must be shielded from background electrical noise. 

Содержание WTCW100 Series

Страница 1: ...Five Boynton Road Hopping Brook Park Holliston MA 01746 USA TEL 508 429 1110 WEB www walchem com WCT WBLW100 Series Cooling Tower and Boiler Controller Instruction Manual...

Страница 2: ...onents are expendable and are not covered by any warranty THIS WARRANTY IS IN LIEU OF ANY OTHER WARRANTY EITHER EXPRESS OR IMPLIED AS TO DESCRIP TION QUALITY MERCHANTABILITY FITNESS FOR ANY PARTICULAR...

Страница 3: ...time Daily Weekly 2 week or 4 week Biocide timers with pre bleed and post add lockout of bleed Intermittent sampling for boilers with proportional blowdown controlling on a trapped sample Time Proport...

Страница 4: ...lly isolated 600 Ohm max resistive load Resolution 0 0015 of span Accuracy 0 5 of reading Agency Approvals Safety UL 61010 1 2012 3rd Ed CSA C22 2 No 61010 1 2012 3rd Ed IEC 61010 1 2010 3rd Ed EN 610...

Страница 5: ...sensor range High end of sensor range Sample period Time Proportional mode 10 seconds 3600 seconds Sample Time Intermittent Sampling mode 0 seconds 3600 seconds Hold Time Intermittent Sampling mode 0...

Страница 6: ...1 Determine the Rate of Steam Production in Pounds per Hour Either read off the boiler name plate water tube boilers or Calculate from horsepower rating fire tube boilers HP x 34 5 lbs hr Example 100...

Страница 7: ...graphs on the next page Use of a flow control valve will give you the best control of the process since the flow rate can be easily adjusted The dial on the valve also gives you a visual indication if...

Страница 8: ...nside the controller even when the power switch on the front panel is in the OFF position The front panel must never be opened before power to the controller is REMOVED If your controller is prewired...

Страница 9: ...Union To Drain To Drain 1 2 3 Figure 4 Typical Boiler Installation Continuous Sampling Install accessories either vertically or horizontally per manufacturer s instructions To Drain Skimmer Blowdown L...

Страница 10: ...10 VOLT AC OUTLET TO SANITARY SEWER COOLING TOWER OPEN SUMP CIRCULATION PUMP X Unions installed for replacement of solenoid or strainer Y Y strainer Z solenoid TYPICAL INSTALLATION SUBMERSION ELECTROD...

Страница 11: ...ivity Electrode TEMP WHT TEMP GRN RCV BLK SHIELD XMT RED SAFETY COVER LABEL R SHLD High Pressure Conductivity Electrode GRN WHT RED BLK Condensate Electrode wiring is typical of all three sensor optio...

Страница 12: ...Effect Flow Meter SHIELD INPUT POWER Chart Recorder SIGNAL SHIELD SHIELD R SHLD Figure 10 Digital Input and Analog Output Wiring 1 2 3 4 5 6 7 8 9 10 11 12 TB2 TB1 FUSE POWER SWITCH POWER SWITCH 1 2 3...

Страница 13: ...U 240V BLK 120V BRN 240V Figure 12 W110 AC Power Relay Output Wiring 1 2 3 4 5 6 7 8 9 10 11 12 TB2 TB1 FUSE POWER SWITCH POWER SWITCH 1 2 3 4 5 6 7 8 9 10 11 12 R1 R2 R3 N N N N L TB3 TB4 TB5 TB6 TB7...

Страница 14: ...er or Lower keys Once the value of the number is correct use the Enter key to store the new value into memory or use the Cancel key to leave the number at its previous value and go back Changing Names...

Страница 15: ...ghted Press the Enter key Press the Scroll Down key until your language is highlighted Press the Confirm key to change all menus to your language Set date if necessary Press the Scroll Up key until Da...

Страница 16: ...ng Setpoint Int Sampling R1 HOA Setting Setpoint Manual R1 HOA Setting Interlock Channels Pulse Prop R1 HOA Setting Setpoint Dual Setpoint R1 HOA Setting Setpoint Probe Wash R1 HOA Setting Input Timer...

Страница 17: ...ter key to get to the Details screen Press the Settings key If the name of the relay does not describe the control mode desired press the Scroll Down key until Mode is highlighted Press the Enter key...

Страница 18: ...ure compensation Enter the temperature of the buffer and press Confirm Buffer Value only appears for One Point Calibration except when automatic buffer recognition is used Enter the value of the buffe...

Страница 19: ...e next reading shown will consist of an average of 10 of the previous value and 90 of the current value Cable Length The controller automatically compensates for errors in the reading caused by varyin...

Страница 20: ...ress the Enter key with an output highlighted to access that output s details and settings NOTE When the output control mode or the input assigned to that output is changed the output reverts to OFF m...

Страница 21: ...and a conductivity limit are set the time limit takes precedence The bleed relay will turn off once the time limit is reached or when the prebleed conductivity limit is reached whichever occurs first...

Страница 22: ...ion from the set point The relay goes through a sequence of activation deactivation as described below The intended purpose of this algorithm is boiler blowdown A sample cannot be supplied to the sens...

Страница 23: ...ontrol Mode Basic Timer Operation When a Probe Wash event triggers the algorithm will activate the relay for the programmed time The relay will activate a pump or valve to supply a cleaning solution t...

Страница 24: ...digital flow meter and continuously adjusts the analog 4 20 mA output proportional band to achieve a target PPM level The user enters the target PPM and the data necessary to calculate the proportiona...

Страница 25: ...troller see Export User Config file below Press the Enter key and then press the Confirm key to transfer those settings to this controller Export User Config File The User Configuration file contains...

Страница 26: ...ays have a fuse to protect the controller from devices connected to the relays that draw excessive current Locate the fuse on the circuit board at the back of the controller enclosure underneath the c...

Страница 27: ...ible Cause Corrective Action No flow Check piping for closed valves blockage etc Check recirculation pump Faulty flow switch cable Check with ohmmeter Faulty controller Check by shorting digital input...

Страница 28: ...ectly Possible Cause Correction Action The software is not functioning If the error message clears on its own no action is required If the error message persists cycle power If the error message still...

Страница 29: ...57 Control Board with AO 191613 Ribbon Cable Controller Parts 103875 Panel 102961 Hanger 102586 Nut 190998 03 Switch assembly 3 ft cable 190996 Float 102919 O Ring 191020 03 Switch Float Assembly 3 ft...

Страница 30: ...191638 03 Electrodeless Conductivity sensor CPVC 3 ft cable 102586 Nut 102594 O ring 191020 03 Flow switch assembly 3 ft cable 190997 03 Switch Float assembly 3 ft cable 102594 O ring 102881 Flow swi...

Страница 31: ...Switch manifold on panel C High pressure contacting conductivity D High pressure contacting cond Flow Switch manifold on panel E Inline submersion 316SS contacting conductivity F 316SS contacting cond...

Отзывы: